Basic Operation - CyberPower CPS7500PRO Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

CPS7500PRO /CPS7500PIE

BASIC OPERATION

BASIC OPERATION
CPS7500PRO
CPS7500PIE
DESCRIPTION
1. AC Outlets
EPS PRO/PIE Series have two general plug-in outlets (UK/Schuko/ France) and one terminal outlet for
connected equipment which ensures temporary uninterrupted operation of the equipment during a power
failure.
Max. Output of 1a is 40A ; Max. Output of 1b is 12A for UK socket, 16A for Schuko/French socket.
Max. Output wattage of (1a+1b) is 5250W.
*Note: Maximum cord length is 10 meters and the cable O.D. must be 10AWG or greater.
2. AC Inlet
AC input terminals
*Note
T he O.D. of the distribution cables must be 10AWG or greater.
: : : :
3. DC Inlet
Battery input terminals
*Note
M aximum battery wiring cable length is 2 meters and the cable O.D. must be 4AWG or greater.
4. DC Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
5. AC Output Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
*Note: Circuit breaker 5a provides max 40A protection for 1a socket.
*Note: Circuit breaker 5b provides max 12A protection for UK socket or 16A for Schuko and France
socket.
6. AC Input Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
7. Charger Circuit Breaker
4