Safety; Electrical Requirements - GE Appliances JP3021 Manuel D'utilisation Et Instructions D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

FOR YOUR SAFETY
• F or Personal Safety, remove house fuse or open
circuit breaker before beginning installation.
Failure to do so could result in serious injury or
death.
• B e sure your cooktop is installed properly by a
qualified installer or service technician.
• To eliminate the risk of burns or fire due to
reaching over heated surface elements, cabinet
storage located above the surface units should
be avoided. If cabinet storage space is to be
provided, the risk can be reduced by installing a
range hood that projects horizontally a minimum
of 5" beyond the bottom of the cabinets. Cabinet
installation above the cooktop may be no deeper
than 13".
• Make sure the cabinets and wall coverings around
the cooktop can withstand the temperatures (up to
200°F) generated by the cooktop.
• Always disconnect the electrical service to the
cooktop before repairing or servicing the cooktop.
This can be done by disconnecting the fuse or
circuit breaker. Failure to do this could result in a
dangerous or fatal shock. Know where your main
disconnect switch is located. If you do not know,
have your electrician show you.
49-2000738 Rev. 3
Installation Instructions

ELECTRICAL REQUIREMENTS

This appliance must be supplied with the proper
voltage and frequency, and connected to an
individual, properly grounded branch circuit,
protected by a circuit breaker or a time delay fuse
as noted on name plate.
We recommend you have the electrical wiring and
hookup of your cooktop connected by a qualified
electrician. After installation, have the electrician
show you where your main cooktop disconnect is
located.
Wiring must conform to National Electrical Code.
You can get a copy of the National Electrical Code,
ANSI/NFPA No. 70-Latest Edition, by writing:
National Fire Protection Association
Batterymarch Park
Quincy, MA 02269
In Canada, wiring must conform to the Canadian
Electrical Code (CEC).
The cooktop conduit wiring is approved for copper
wire connection only, and if you have aluminum
house wiring, you must use special UL approved
connectors for joining copper to aluminum. In
Canada, you must use special CSA approved
connectors for joining copper to aluminum.
You must use a two-wire, three conductor 208/240
VAC, 60 Hertz electrical system. A white (neutral)
wire is not needed for this unit. The cooktop must be
installed in a circuit that does not exceed 125 VAC
nominal to ground.
Refer to the name plate on your cooktop for the KW
rating for your cooktop.
Name plate location
KW Rating
KW Rating 240v
208V
≤4.8KW
≤4.1 KW
4.9 KW - 7.2 KW
4.2 KW - 6.2 KW
7.3 KW - 9.6 KW
6.3 KW - 8.3 KW
9.7 KW - 12.0 KW
8.4 KW - 10.4
Recommended
Circuit Size
(Dedicated)
20 Amp
30 Amp
40 Amp
50 Amp
KW
13

Publicité

Table des Matières
loading

Table des Matières