05-351 / 05-352 / 05-336 / 05-300
LOAD TABLE for 05-351
Type of load
Resistive: incandescent
lamps, halogens 230V...
Inductive:
Low-voltage lighting via
ferromagnetic transformers
(transformer load = minimum 85%)
Non- or series compensated
fluorescent lighting
with ferromagnetic ballasts
Parallel compensated
fluorescent lighting
with ferromagnetic ballasts
ECG: electronic control gear
(HF fluorescent loads,
electronic transformers...)
56
Symbol
Max. load
230V 50Hz
10A
2300W
2,6A 600VA
10A
2300VA
2,6A 600W
4A
920VA
EN