11. The following tests were additionally conducted at specified conditions as
noted below, in accordance with the Standard for Industrial Control Equip-
ment, UL 508A, 17th Edition.
Temperature Test: Models SDU 850 and SDU 500 were mounted in an enclo-
sure (150% of the dimensions of the device, overall 420 by 180 by 160 mm),
in accordance with par. 42.6 of UL 508A. The suitability usage of industrial
control equipment shall be considered in end application.
Breakdown of Components Test: Model SDU 850 had been conducted through
a 30-ampere non-time-delay fuse, in accordance with par. 57.5 of UL 508A.
12. The products, Models SDU 850 and SDU 500 were evaluated based on
Pollution Degree 3 and Overvoltage Category III criteria and a minimum
end use ambient of 40°C, so that these devices do not have to be
derated when installed within an industrial control panel.
14.0 Product Registration & Warranty Information