Application area
Elztrip EZ100 has a single heating panel and is
designed for ceiling heights between 2.5 and 4
metres. EZ100 is used in shops, schools, exhibition
halls, workshops and hospitals. Private homes and
offices are also common areas of use.
EZ100 is suitable both for total and
supplementary heating, as well as for protection
against cold draughts from large glass surfaces.
Protection class: IP44
Operation
The panels have an operating temperature of up to
o
280
C and the heat is radiated to cold surfaces.
Heating with radiant heaters is very energy
effecient and a high comfort level is obtained.
Mounting
Elztrip EZ100 is mounted on the ceiling, on arma-
ture rails or suspended from the ceiling by means
of rods or chains. EZ100 is intended for permanent
installation and should always be mounted
horizontally. In rooms frequently used, the heater
should be mounted 1.5 to 2 metres above head
height, see Fig. 3. The distance between the panels
should not be more than the height between panel
and floor, i.e "a" should be less than "H" , see Fig.
3. For minimum mounting distance, see Fig. 4.
Ceiling fixtures and screws are found inside the
connection box.
Mounting on the ceiling
1 Mount the ceiling fixtures on the ceiling.
2 Open the folded mounting hinges on the
top side of the heater and hang the heater
on the ceiling fixtures. See Fig. 1. Make
sure that the guide pegs are fitted into the holes,
to ensure that the heater is fixed in a horizontal
position. Fasten the screws.
Mounting on the wall (only horizontal)
Brackets for wall mounting (EZMVK) are extra.
1 Mount the bracket on the wall.
2 Open the folded mounting hinges on the
top side of the heater and hang the heater on the
brackets. See Fig. 2. Make
pegs are fitted into the holes, to ensure that the
heater is fixed in a horizontal position. Fasten the
screws.
8
Elztrip EZ 100
Installation and operating instructions
sure that the guide
Connection
The terminal box cover has self-tapping screws.
The screw should only be unthreaded 1,5 turns,
after which the cover can be
the screw is self-tapping, the thread is vunerable to
damage if the screw is fully removed and replaced
several times. EZ100 is intended for 230V~ and
permanent installation. The heater(s) should only be
wired by a competent electrician, and in
accordance with existing national regulations. The
appliance should be preceded by a double pole
switch with at least 3 mm breaking gap. There are
two holes with cable glands Ø 21mm on the top of
the connection box. Connection and serial
connection of EZ100 is done with a maximum
2
cable size of 4x2.5 mm
Safety
• Do not touch surface of heater when in use!
• The unit must not be covered fully or
partially with clothes or similar materials,
as covering can result in a risk of fire!
Circuit breaker
If the installation is protected by means of a circuit
breaker and it trips when the appliance is
connected, this may be due to moisture in the
heating element. When an appliance containing
heating element has not been used for a long time
and is stored in a damp environment, moisture can
enter the element. This should not be seen as a
fault, but is simply rectified by connecting the
appliance to the mains supply via a socket without
a circuit breaker, so that the elements dry. The
drying time can vary from a few hours to a few
days. As a preventive measure the unit should
occasionally be run for a short time during long
operation pauses. At large installations, there should
be a division on several circuit breakers.
Maintenance
If the heater is used in rooms where there are
aerosols, lacquer, solvents and similar, this can
cause a coating on the panels and discolour them.
The output is not affected.
removed. NB While
+ earth.