Exterior Ducting Installation; Weatherhood Location; Installing The Ducting To The Weatherhood; Steps For Hood Installation - Direct Air PHRVR100 ES Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EXTERIOR DUCTING INSTALLATION

WEATHERHOOD LOCATION

• Decide where your intake and exhaust hoods will be located.
Locating the Intake Weatherhood
• Should be located upstream (if there are prevailing winds) from the
exhaust outlet.
• At a minimum of 2m (6') away from dryer vents and furnace exhaust
(medium or high efficiency furnaces), driveways, oil fill pipes, gas meters,
or garbage containers.
• At a minimum height of 460mm (18'') above the ground, or above the level
of expected snow accumulation.
• At a minimum distance of 1m (3') from the corner of the building.
• Do not locate in the garage, attic, crawl space, or underneath deck.
Locating the Exhaust Weatherhood
• At least 460mm (18") above ground or above the depth of expected snow accumulation
• At least 1m (3') away from the corner of the building
• Not near a gas meter, electric meter or a walkway where fog or ice could create a hazard
• Do not locate in a garage, workshop or other unheated space
INSTALLING THE DUCTING TO THE WEATHERHOODS
A well designed and installed ducting system will allow the HRV to operate at its
maximum efficiency. The inner liner of the flexible insulated duct must be secured to the
sleeve of the weatherhood (as close to the outside as possible) and to the appropriate duct
connection on the HRV. The insulation should remain full and not crushed. The outer liner,
which acts as a vapor barrier, must be completely sealed to the outer wall and the HRV
using tape and/or caulking. A good bead of high quality caulking (preferably acoustical
sealant) will seal the inner flexible duct to both the HRV duct connection and the
weatherhood prior to securing them.
To minimize airflow restriction, the flexible insulated duct that connects the two outside
weatherhoods to the HRV should be stretched tightly and be as short as possible.
Twisting or folding the duct will severely restrict airflow.
See "Installation Diagram Examples" for installation examples.

STEPS FOR HOOD INSTALLATION:

1 Using the duct connection of
the outside hood, outline the
intake & exhaust holes to be
cut. The holes should be slightly
larger than the duct connection
to allow for the thickness of the
insulated flexible duct. Cut a
hole for both the intake and
exhaust hoods.
2 Pull the insulated flexible duct
through the opening until it is
well extended and straight.
Slide the duct's inner vinyl sleeve
over the hood duct connection
and secure. Pull the insulation
over the duct and pull the vapor
barrier over the sleeve. Secure
with appropriate tape or
sealant.
OUTSIDE CORNER
36" (1m)
min.
INTAKE
18" (460mm) min.
3 Push the hood into the opening
and then attach the hood to the
outside wall with mounting
screws.
Repeat the installation
procedure for both the supply
and exhaust hoods.
INSIDE CORNER
36" (1m)
min.
6' (2m)
min.
EXHAUST
18" (460mm) min.
4 Using a caulking gun, seal
around both hoods to prevent
any leaks.
11

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Phrvr104 esPhrvr 150

Table des Matières