S19-270C, S19-270E, S19274C, S19274E
Installation
—
Halo eye/face wash right-hand unit is shown on a sample 25" deck. Other units are similar. For classic eye/face wash
installation, refer to the dimensions on page 5 to determine optimal mounting position. Refer to page 8 for left-hand units.
Minimum dimensions necessary to contain splashing from Halo units are shown.
Apply pipe sealant (supplied by installer) to all male-threaded pipe joints. The top of the eyewash heads should be positioned
a minimum of 33" (838mm) and a maximum of 45" (1143mm) from the floor and 6" (152mm) from the nearest obstruction.
Proper faucet shank/handle
clearance and recommended
minimum splash containment
dimensions must be considered
when selecting the desired
location for mounting.
25"
(635mm)
Connect the water supply using
C
piping (supplied by installer) with
½" NPT female threaded end .
8
Eye/Face Wash
"ON" Position
E
2/5/2015
A
2"
(51mm)
Ø ³⁄₁₆"
Ø 1¹⁄₈"
Deck Mounting Pattern
Drill (3) holes as shown .
13⁷⁄₈"
(352mm)
Radius
(64mm)
Slowly open the water
supply lines to relieve air
and pressurize the valve .
Test the unit for leaks
and adequate flow .
B
Deck
"OFF" Position
13"
(330mm)
Ref .
9¼"
(235mm)
Ref .
5¾"
(146mm)
Ref .
2¹⁄₈"
(54mm)
Min .
2½"
Min .
D
To
Wall
Bradley • 215-1326 Rev. U; ECN 13-05-032
Installation