Halo eyewash right-hand unit is shown on a sample 25" deck. Other units are similar. For classic eyewash installation,
refer to the dimensions on page 4 to determine optimal mounting position. Refer to page 8 for left-hand units.
Minimum dimensions necessary to contain splashing from Halo units are shown.
Apply pipe sealant (supplied by installer) to all male-threaded pipe joints. The top of the eyewash heads should be
positioned a minimum of 33" and a maximum of 45" from the floor and 6" from the nearest obstruction.
Proper faucet shank/handle
clearance and recommended
minimum splash containment
dimensions must be considered
when selecting the desired
location for mounting.
25"
(635mm)
Connect the water supply using
C
piping (supplied by installer) with
½" NPT female threaded end .
Bradley • 215-1326 Rev. U; ECN 13-05-032
Eyewash
"ON" Position
E
A
2"
(51mm)
Ø ³⁄₁₆"
Ø 1¹⁄₈"
Deck Mounting Pattern
(drill (3) holes as shown)
8"
(203mm)
Radius
2"
(51mm)
Ref .
Slowly open the water
supply lines to relieve air
and pressurize the valve .
Test the unit for leaks
and adequate flow .
2/5/2015
S19-270C, S19-270E, S19274C, S19274E
B
Deck
"OFF" Position
7¾"
(197mm)
5¾"
Ref .
(146mm)
Ref .
2⁵⁄₈" (67mm)
Ref .
5¼"
(133mm)
Min .
¾" (19mm)
Min .
D
To
Wall