Installation method (continued)
When take Malfunction monitor output, or take Bypass
5
operation monitor output.
Bypass operation indicator
Monitor output
Power
terminal TM3
Supply
Lamp or
monitoring unit
Malfunction indicator
Connect to 6 and 7, or 7 and 8 of the monitor output terminal
block (TM3) with reference to the wire connection diagram.
Note
* Don't tighten screws of terminal block with a torque larger than 0.5 Nm.
It could damage the PCB.
Bypass or Delay 2 monitor output with delay function 2 can be possible.
"Setting for TM3 67")
(Refer to function settings
13
When connect to an Electrically operated damper, or take
6
Operation monitor output
Connect the power supply cable from the Electrically operated damper to
9 and 0 of the monitor output terminal block (TM4) with reference to
the wire connection diagram.
Operation monitor output with delay function 1 can be possible.
"Setting for TM4 90")
(Refer to function settings
6
Power Supply
Monitor output
terminal (TM4)
Electrically
operated
damper
Lamp
Note
* Don't tighten screws of terminal block with a torque
larger than 0.5 Nm. It could damage the PCB.
* Response times to external input signals are
as shown in the following table.
When switching High/Low/Extra-Low fan speed externally
7
(when CO
sensor or other equipment is connected)
2
Using marketed CO
sensor, etc., make connection by inserting the
2
optional remote ON/OFF adaptor (PAC-SA88HA-E) in the connector CN16
(High/Low selector) as shown by the figure.
To force High fan speed externally
CO
sensor, etc.
Remote ON/OFF adaptor
2
(When CO
increases: Closed)
(Optional) PAC-SA88HA-E
2
SW1
SW1: High fan speed operation switch
Not used. Insulate completely.
(When closed: For High fan speed operation)
Max wiring length 32 ft (10 m)
When SW1 is "ON", fan speed of the Lossnay will be set to "High" (Extra-
High) regardless of the remote control setting.
Use this in such a way that it ventilates at Low or Extra-Low fan speed
normally, and when the external sensor detects contamination of indoor
air, it changes to High (Extra High) fan speed operation.
To force Low fan speed externally
CO
sensor, etc.
Remote ON/OFF adaptor
2
(When CO
decreases: Closed)
(Optional) PAC-SA88HA-E
2
SW1
SW1: Low fan speed operation switch
Not used. Insulate completely.
(When closed: For Low fan speed operation)
Max wiring length 32 ft (10 m)
When SW1 is "ON", fan speed of the Lossnay will be set to "Low"
regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed normally, and
when the external sensor detect that the indoor air contamination is
low, it changes to Low fan speed operation.
Bypass operation signal
contactor rating
6
Max 240 VAC, 1 A
24 VDC, 1 A
7
Min 220 VAC, 100 mA
5 VDC, 100 mA
8
Malfunction signal
0
9
Contactor rating
Max 240 VAC, 2 A
24 VDC, 2 A
Min 220 VAC, 100 mA
5 VDC,
100 mA
External Signal Response Time
Level Signal
Max. 7 sec.
Pulse Signal
Max. 200 msec
Lossnay
control board
Brown 1
CN16
Red 2
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Lossnay
control board
Brown 1
Red 2
CN16
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
To force Extra-Low fan speed externally
CO
sensor, etc.
2
(When CO
decveases: Closed)
2
SW1
SW1: Low fan speed operation switch
Not used. Insulate completely.
(When closed: For Low fan speed operation)
Max wiring length 32ft (10 m)
When SW1 is "ON", fan speed of the Lossnay will be set to "Extra-Low"
regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed normally, and
when the external sensor detects that the indoor air contamination is
low, it changes to Extra-Low fan speed operation.
* For LGH-F1200RX
, fan speed of the Lossnay will be "Low".
5
8
When switching Bypass externally.
Establish the wire connection by inserting the optional remote ON/OFF
adaptor (PAC-SA88HA-E) in the connector CN16 (Ventilation mode
selector).
Remote ON/OFF adaptor
(Optional) PAC-SA88HA-E
SW1
Not used. Insulate completely.
SW1: Bypass ventilation operation switch
(When closed: For Bypass ventilation operation)
Max wiring length 32 ft (10 m)
With SW1 is "ON", the ventilation mode of Lossnay is changed to the
Bypass ventilation regardless of the setting on the remote controller.
* When the outdoor air temperature drops lower than 46.4˚F (8˚C), it
changes to the heat exchanger ventilation. (Display of the remote
controller does not change.)
When using the remote/local switching and the ON/OFF input
9
(level signal)
The remote controller (PZ-41SLB-E) cannot be used.
Insert the optional remote ON/OFF adaptor (PAC-SE55RA-E) in CN32 on
the Lossnay control PCB.
Remote
control board
Relay circuit
SW2
X
X
SW1
Y
Y
SW1: When this is ON, Lossnay cannot turn ON/OFF by the Remote
Controller (PZ-60DR-E, PZ-52SF-E).
SW2: When SW1 is ON, Lossnay can be turned ON by setting SW2 at
ON or turned OFF by setting SW2 at OFF.
SW1: Remote/local selector switch
SW2: ON/OFF switch
X, Y : Relay (Contactor rating DC 1 mA)
When connecting to the City Multi, Lossnay remote controller (PZ-52SF-
10
E) or Mitsubishi Electric Air-Conditioner Network System (MELANS)
* If centralized control is performed according the wire connection
shown in this section, the remote controller (PZ-41SLB-E) cannot be
used.
M-NET transmission cable input terminal block
Remote ON/OFF adaptor
Lossnay
(Optional) PAC-SA88HA-E
control board
Brown 1
Red 2
CN16
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Lossnay
control board
Brown 1
Red 2
CN16
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Remote ON/OFF adaptor
Lossnay
(Optional) PAC-SE55RA-E
control board
Orange 1
CN32
Red 2
Brown 3
Max wiring length 32 ft (10 m)
TB5
A
B
S
Shielded wire
M-NET transmission cable
9