Mounting Base Unit And Cover Cabinet; Unit Disassembly; Checks Before Startup; Use - Galletti ART-U Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

MOUNTING BASE UNIT AND COVER CABINET

Upon receipt of the unit, check the integrity of the package.
Leave the cabinet inside the packaging and proceed with the
installation of the base unit (which also includes the air outlet
grille, in the upper part) to the wall using the 4 slots provided
and the screw anchors suitable for the characteristics of the sup-
porting wall, keeping the bottom edge at least 100 mm above
the floor to ensure a correct intake of air and facilitate the filter
removal.
Once the installation of the base unit (which also includes the
hydraulic and electrical connections) is completed, it is possi-
ble to proceed with the assembly of the covering cabinet (front

UNIT DISASSEMBLY

To disassemble the unit, carefully follow the steps listed below:
1. Remove the power supply to the machine by the dedicated
disconnectory.
2. Remove air filter acting on allen screws (see figure 11.11 p.
71 )
6

CHECKS BEFORE STARTUP

Ū Check that the unit is properly levelled and that the drainage
outlet is not clogged (by masonry debris, etc.)
Ū Check that the unit is installed in such a way as to guarantee
the proper air flow.
Ū Check the tightness of the plumbing connections (to the ex-
changer and condensate drainage line).
7

USE

To use the fan coil refer to the instructions on the control panel
available as accessory.
The air flow may be directed as desired using the upper FLAP
(flow may be directed upward or downward) as well as the sec-
ond row of louvers (for directing air flow either to the left or
right) as shown in figure 11.2 p. 64  and 11.3 p.64.
24
ART-U
panel and side panels)
In order to fix the cabinet, proceed with positioning it near the
base unit, so as to align the support pins with the slots on the
rear panel (see figure 11.12 p. 72 ).
Then, lower the cabinet so as to obtain the locking of the pins
inside the appropriate seats.
To prevent disassembly of the cabinet, it is necessary to act
on the lower locking screw, with the appropriate Allen key, as
shown in the figure 11.12 p. 72 .
Mount the air filter with allen screws (see figure 11.11 p. 71 )
Then power supply to unit.
3. Unscrew the side screws and lift the cabinet by removing the
fastening pins from the slots.
4. Perform the above operations in reverse order before re-
starting the unit.
Ū Make sure the electric wires are tightly connected (carry out
this check with the power supply OFF).
Ū Make sure that air has been eliminated from the heat ex-
changer.
Ū Reapply the cabinet and filter
Ū Power the fan coil and check its performance
ATTENZIONE: For safety reason, do not introduce your fin-
gers or other pointed objects in the air outlet grilles.
DANGER:
The unit may be used by children of at least 8
years of age and by persons with reduced physical, sen-
sory, or mental capabilities, or who lack experience or the
necessary knowledge, provided that they are supervised or
after they have received instructions relating to the safe use
of the unit and understand the inherent dangers. Children
must not play with the unit. Cleaning and maintenance to
be carried out by the user must not be performed by unsu-
pervised children.