EASYREC120
7.
Recovery cylinder cooling method
7.1.
P
-
C
RE
WORK
a) Before starting, there must be at least 0,5 kg of liquid refrigerant in the cylinder
b) Make sure all connections are correct and tight (refer to the below picture)
c) Make sure the OUTPUT valve and INPUT valve are on position CLOSE.
d) Turn the Recover/Purge valve to position "Recover".
e) Power on and then press the START key to start the unit.
f)
Open the Vapour and Liquid valves on the recovery cylinder.
g) Open the OUTPUT valve, then open the INPUT valve.
h) Regulate the OUTPUT valve so that the output pressure is 7 bar higher than the input pressure,
but never more than 21 bar
i)
Run until the cylinder is cold; then turn the unit off.
WIGAM
USER'S MANUAL
OOLING METHOD
ENGLISH
37