INSTALLATION INSTRUCTIONS
84

Installer Setting - Static Pressure Step Setting

This function is applied to only duct type. Setting this in other cases will cause malfunction.
This function is only available on some models.
This is the function that static pressure of the product is divided in 11 steps for setting.
• Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32) setting
is being used.
• For the static pressure value for each step, refer to the indoor unit in the product manual.
1
If pressing
button long for 3
seconds, it enters into Thermostat
installer setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
If pressing
button repeatedly, it
2
moves to static pressure selection menu
as picture below.
3
Select static pressure by pressing
button.
00: use static pressure (code 06) set value
01~ 11: static pressure step (code 32) set
value
pressure
Function Code
Press
button to save.
4
5
Pressing
button will exit settings
mode.
❈ After setup, it automatically gets out
of setup mode if there is no button
input for 25 seconds.
❈ When exiting without pressing set
button, the manipulated value is not
reflected.