Ingersoll Rand R4-11 kW Mode D'emploi page 32

Masquer les pouces Voir aussi pour R4-11 kW:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
Bit 0: Host/Local (R/W)
0 = Local
1= Host
Bit 1: Run/Stop (R/W)
0 = Stop
1 = Run
Bit 2: Load/Unload (R/W)
0 = No Loaded Operation
1 = Loaded Operation
Bit 3: operating at Minimum Speed (R)
0 = Operating above Minimum Speed
1 = Operating at Minimum Speed
Bit 4: operating at Maximum Speed (R)
0 = Operating below Maximum Speed
1 = Operating at Maximum Speed
Bit 5: Stopped in Auto Restart (R)
0 = Not Stopped in Auto Restart
1 = Stopped in Auto Restart
Register 98: Compressor Type
55 = 5.5 kW
75 = 7.5 kW
80 = 7.5 hp
100 = 10 hp
110 = 11 kW
150 = 15 kW
200 = 20 hp
220 = 22 kW
290 = 30 hp
300 = 30 kW
400 = 40 hp
370 = 37 kW
500 = 50 hp
Register 127 & 128:Day
EN-32
RELEASED 16/Dec/2014 10:49:53 GMT
Table 13 : Xe 70M Variable Speed Controller Register 01-Status/Control
Table 14 : Xe 70M Variable Speed Controller Register Codes
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
Bit 6: Alarm (R)
0 = No Alarms
1 = Alarms
Bit 7: Warning (R)
0 = No Warnings
1 = Warnings
Bits 8 -9: Normal/Unload operate (R)
00 = Unloaded Operation
11 = Normal Operation
Bits 10 –11: Unused
Bit 12: Fixed/Variable Speed Compressor (R)
0 = Fixed Speed
1 = Variable Speed
Bits 13-15: Unit Type (R): Unused
4 = Thursday
7 = Daily
5 = Friday
8 = Weekdays
6 = Saturday
9 = Weekends
80448483 Rev.B