Electrical equipment may only be used on the work platform under the following conditions:
D
D
Only use the work platform in the vicinity of such units under the following conditions:
D
D
3. Technical description
• Before commencing assembly of the platform, check that all parts shown are in-
3.1 Scope of delivery
• Contact the manufacturer if any parts are missing.
ANGER
ANGER OF ELECTRIC SHOCKS WHEN WORKING WITH ELECTRICAL EQUIPMENT ON THE WORK PLATFORM
> With protective low voltage (48 V).
> with protective insulation (separation transformer).
> if the equipment is connected via a ground fault circuit interrupter with a resid-
ual current of max. 30 mA.
ANGER
ANGER OF ELECTRIC SHOCKS WHEN WORKING IN THE VICINITY OF CURRENT
> The unit in question must be disconnected and secured against being switched
back on.
> The section of the unit in question must be de-energised.
> The section of the unit must be short-circuited by means of a ground rail.
> The section of the unit must be insulated against any adjacent current-bearing
components.
ANGER
ANGER OF ELECTRIC SHOCKS WHEN WORKING IN THE VICINITY OF POWER LINES
> When working near power lines, observe the safety clearances listed in the fol-
lowing table.
> When calculating safety clearances, allow for the swinging radius of power
lines and the movement radius of working personnel. The movement radius in-
cludes any objects held by personnel.
> If it is not possible to comply with the safety clearances, have the operating au-
thority disconnect the power lines and secure them against being switched
back on.
Rated voltage (V)
< 1000 V
1 kV – 110 kV
110 kV – 220 kV
220 kV – 380 kV or if the rated
voltage is not known
cluded in the delivery and are in perfect condition. Only original parts in perfect
condition may be used for assembly of the work platform.
To see the scope of delivery, turn to the
illustrations section of the manual.
-
!
BEARING UNITS
!
Safety clearance (m)
1.0 m
3.0 m
4.0 m
5.0 m
!