Mitsubishi Electric Mr. SLIM SEZ-M25DA Manuel D'installation page 19

Table des Matières

Publicité

9. Test run
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
14
No sound
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Beeper sounds/OPERATION INDICATOR
lamp flashes (Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does
not come on, there are no error records.
*2 If the beeper sounds three times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)" after the initial two beeps to confirm the self-check start signal was
received, the specified refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed on the LCD.
• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Wired remote controller
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not appear
even when operation switch is
turned ON (operation lamp does
not light up).
On the wireless remote controller with conditions above, following phenomena takes place.
• No signals from the remote controller are accepted.
• OPE lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED 1 (power for microcomputer)
LED 2 (power for remote controller)
LED 3 (communication between indoor and outdoor units)
Wired remote
controller
Check code
P1
Intake sensor error
P2, P9
Pipe (Liquid or 2-phase pipe) sensor error
E6, E7
Indoor/outdoor unit communication error
P4
Drain sensor error
P5
Drain pump error
P6
Freezing/Overheating safeguard operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4
Remote controller signal receiving error
Fb
Indoor unit control system error (memory error, etc.)
PL
Refrigerant circuit abnormal
– –
No corresponding
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating safeguard operation
Abnormal temperature of heat sink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal
synchronous signal to main circuit/Current sensor error
Other errors (Refer to the technical manual for the outdoor unit.)
Symptom
LED 1, 2 (PCB in outdoor unit)
For about 2 minutes
After LED 1, 2 are lighted, LED 2 is turned off,
following power-on
then only LED 1 is lighted. (Correct operation)
Only LED 1 is lighted. → LED 1, 2 blink.
After about 2 minutes
has expired following
power-on
Only LED 1 is lighted. → LED 1, 2 blinks
twice, LED 2 blinks once.
Indicates whether control power is supplied. Make sure that this LED is always lit.
Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
indoor unit which is connected to the outdoor unit refrigerant address "0".
Indicates state of communication between the indoor and outdoor units. Make sure that this LED is
always blinking.
Symptom
Symptom
• For about 2 minutes after power-on, operation of the
remote controller is not possible due to system start-up.
(Correct operation)
• Connector for the outdoor unit's protection device is not
connected.
• Reverse or open phase wiring for the outdoor unit's power
terminal block (L1, L2, L3)
• Incorrect wiring between indoor and outdoor units
(incorrect polarity of S1, S2, S3)
• Remote controller wire short
Remark
Remark
For details, check the LED
display of the outdoor controller
board.
Cause
19

Publicité

Table des Matières
loading

Table des Matières