With capacitive load, connecting cables longer than 50m or
connection to a PLC with capacitive input circuit, a 22Ω resi-
stor is required to be connected in series to limit current
spikes.
Warning!
Overloading the magnetic switches may lead to the destruc-
tion of the reed switch, which may cause a malfunction to
the control circuitry and harm to persons or goods. The ma-
ximum switch capacity values given on the tag label must
not be exceeded.
Level Transmitter (only Typ BMG)
The level transmitter must be connected according to the
wiring diagram printed on the transmitter and wired to the
electronic evaluation unit in series.
A screened cable must be used and earthed at one end for
long lines or if the cables are laid together with power
cables.
BU
BN
BK
Internal connection diagram
The cable gland must then be sealed and the lid of the ter-
minal box be closed tightly.
Two-wire Head Transducers (Typ BMG)
The principle connection of Two-wire headmounted trans-
mitters is shown in the wiring diagramm below.
The wiring diagram of the actualy used transmitter should be
observed.
22R
BU
BN
BK
100%
BU
R2
BN
R1
BK
0%
Potentiometer equivalent cirquit
4 - 20mA
+
A
R
12 - 30V DC
I
-
Ri