SECTION 1 |
Installation environment
• The inverter should be installed indoor only in a well ventilated, cool, dry environment.
• Do not expose to moisture, rain, snow or liquids of any type.
• To reduce the risk of overheating and
openings of the cooling fan.
• To ensure proper ventilation, do not install in a low clearance compartment.
Preventing fire and explosion hazards
• Working with the unit may produce arcs or sparks. Thus, the unit should not be used
equipment. These areas may include spaces containing gasoline-powered machinery,
fuel tanks, and battery compartments.
Precautions when working with batteries
• Batteries contain very corrosive diluted Sulphuric Acid as electrolyte. Precautions
should be taken to prevent contact with skin, eyes or clothing.
• Batteries generate Hydrogen and Oxygen during charging resulting in evolution of
explosive gas mixture. Care should be taken to ventilate the battery area and follow
the battery manufacturer's recommendations.
• Never smoke or allow a spark or
• Use caution to reduce the risk of dropping a metal tool on the battery. It could spark
or short circuit the battery or other electrical parts and could cause an explosion.
• Remove metal items like rings, bracelets and watches when working with batteries.
The batteries can produce a short circuit current high enough to weld a ring or the
like to metal and, thus, cause a severe burn.
• If you need to remove a battery, always remove the ground terminal from the battery
Make sure that all the accessories are off so that you do not cause a spark.
1.3 SAFETY INSTRUCTIONS - INVERTER RELATED
Preventing Paralleling of the AC Output
The AC output of the unit should never be connected directly to an Electrical Breaker
Panel / Load Centre which is also fed from the utility power / generator. Such a direct
connection may result in parallel operation of the different power sources and AC power
from the utility / generator will be fed back into the unit which will instantly damage
Breaker Panel / Load Center is fed from this unit and this panel is also required to be fed
from additional alternate AC sources, the AC power from all the AC sources (like the
utility / generator / this inverter) should
Switch and the output of the Selector Switch should be connected to the Electrical Breaker
Panel / Load Center.
4
4 | SAMLEX AMERICA INC.
4
Safety Instructions
do not obstruct the suction and discharge
near the batteries.
be fed to an Automatic / Manual Selector
Electrical