Menu Frst (fig.4)
4 4
1
2
Press the SET button to access the "FrSt" menu; the
following menu options can be displayed using the UP
and DOWN buttons, and selected with the SET button:
- Unbl: enable no-frost function with unbalanced air
flows; the parameter can be attributed one of two
values, displayed using the UP and DOWN buttons
and selected with the SET button:
no-frost function with unbalanced air flows;
disables no-frost function with unbalance air flows.
- HEAt: enable no-frost function with preheating; the
parameter can be attributed one of two values,
displayed using the UP and DOWN buttons and
selected with the SET button:
On: enables no-frost function with preheat (only with
preheater installed);
Off: disables no-frost function with preheat (only
without preheater installed);
Menu Al (fig.5)
5 5
1
2
Press the SET button to access the "Al" menu; this is
used for the sole purpose of viewing messages
associated with current error situations, which are
displayed by pressing the UP and DOWN buttons. The
error situations envisaged are listed below (for possible
actions, see the table under "Error management").
ER01: indoor ntc faulty.
ER02: outdoor ntc faulty.
ER03: not used / optional functions
ER04: exhaust ntc faulty.
ER05: supply ntc faulty.
ER06: lcd panel not installed (with relative selected
parameter active).
10
SKP10
3
4
5
6
7
On:
SKP10
3
4
5
6
7
ER07: preheater faulty, or missing.
ER08: outdoor temperature higher than 45 °C.
ER09: indoor temperature higher than 45 °C.
ER10: replace filters
Menu Temp (fig.6)
esc
6 6
set
Press the SET button to access the "Temp" menu; the
enables
following menu options can be displayed using the UP
O F F :
and DOWN buttons, and selected with the SET button:
- Tout: outdoor temperature;
- Tin: indoor temperature;
- Te: exhaust temperature;
- Tsup: supply temperature
Menu Mbus (HRI-E: FULL version only) (fig.7)
7 7
esc
set
Press the SET button to access the "Mbus" menu, the
following menu options can be displayed using the UP
and DOWN buttons, and selected with the SET button:
- Addr: address of Modbus device; the parameter can
be attributed values from 1 to 255, displayed using the
UP and DOWN buttons and selected with the SET
button (the default value is 1);
- Baud: transmission rate: the parameter can be
attributed 3 values: 3 -> 9600, 4 -> 19200, 5 -> 38400
(default).
- Par: parity bit; the parameter can be attributed three
values, displayed using the UP and DOWN buttons
and selected with the SET button:
1: EVEN
2: NONE
3: ODD (default EVEN)
1
2
3
4
5
6
7
1
2
3
4
5
6
7
SKP10
esc
set
SKP10
esc
set