Dometic COOLMATIC CRX50 Pro Instructions De Montage Et De Service page 25

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

CRX50 Pro, CRX65 Pro
Number of
Fault
flashes
3
The motor doesn't start The rotor is jammed.
4
Speed too low
5
Overheating of the
electronics unit
Constantly
Temperature sensor
errors
Compressor does not run (battery connection)
Problem
U
= 0 V
Term
U
≤ U
Term
CON
Start attempt with
U
≤ U
Term
OFF
Start attempt with
U
≥ U
Term
ON
EN
Possible cause
The pressure difference in the cooling system
is too high (> 5 bar)
If the cooling system is overloaded, the mini-
mum speed of the motor of 1,850 rpm can-
not be maintained
If the cooling system is loaded too heavily or
the temperature is set too high, the electron-
ics can overheat
Temperature sensor is defective
Possible cause
There is an interruption in the
battery – electronics connection
Main switch faulty (if installed)
Additional supply line fuse has blown
(if installed)
Battery voltage is too low
Loose cables
Poor contact (corrosion)
Battery capacity too low
Cable cross section too small
Ambient temperature too high
Insufficient ventilation
Condenser is dirty
Troubleshooting
Remedy
Establish a connection
Replace the main switch
Replace the supply line
fuse
Charge the battery
Establish a connection
Replacing the battery
Replace the cable
(fig. 0, page 8)
Move the refrigerator to
another location
Clean the condenser
25