Bottom Installation
Horizontal Duct
Air ow
1000 cfm min.
min 8" 200 mm
24" min
Upstream
36" min
Downstream
Fig. 3.i
3.7
STEAM MANIFOLD (12" & 17.5" OPTIONS AVAILABLE)
For certain applications, a longer steam manifold may be required. Select an accessible location on the duct, allowing at least
36" of straight duct (no elbows or obstructions) after the point where the steam manifold will be installed and the clearances can
be maintained as per the following drawings.
To mount the steam manifold, cut or drill a 2-1/2" hole in the duct (See Fig. 3.i). Apply caulk to the mounting plate of the manifold.
Attach the steam manifold to the duct using (4) #10 sheet metal screws (supplied). Install end bracket to maintain correct slope.
IMPORTANT: Allow 5 feet (1-1/2 m) of straight return duct downstream of the distributor pipe or nozzle for absorption of
the steam. Always allow 3 feet (0.9 m) of straight supply duct upstream of the distributor manifold or nozzle for evaporation of
the steam. Turbulent air flow may require longer lengths.
The return condensate hose from the steam nozzle / steam manifold must be trapped. Coil the hose into a vertical loop and
secure it below the steam nozzle / steam manifold. This trap prevents steam from being released into the cabinet. The end of the
¼" ID hose may be run through the knockout at the top of the humidifier and inserted into the hole located on top of the fill cup.
steam inlet
condensate drain
X
screws max. dia. "M5"
Fig. 3.j
Side Installation
Horizontal Duct
=
=
ange gasket
L
(see table on above)
Y
B
hole in wall
Optional stainless-steel steam manifold
USA: 25-10 12" or 25-11 17.5" Canada: GF-DP030 Kit 12" or GF-DP045 Kit 17.5"
H > 8"
Air ow
1000 cfm. min
1/3 height
fasten the manifold support bracket
22 (0.87")
A
10 (0.39")
B
58 (2.28")
Y
35 (1.38")
68 (2.68")
X
dimensions in mm (inches)
use the manifold support bracket, supplied, to ensure
the 2° slope due to the shape of the ange
10
10
Side Installation
Vertical Duct
Air ow
=
Air ow
=
1000 cfm. min
30 (1.18")
10 (0.39")
68 (2.68")
45 (1.77")
77 (3.03")
min 8" 200 mm