INSTALLATION INSTRUCTIONS FOR THE
MICRO SWITCH GLS DIN SERIES
GLOBAL LIMIT SWITCH
Instrucciones de instalación para los MICRO SWITCH interruptores limite global (serie GLS-DIN)
Einbauanweisungen für den MICRO SWITCH Global Endschalter (Serie GLS-DIN)
Instructions d'installation du MICRO SWITCH fin de course mondiales (série GLS-DIN)
Istruzioni per l'installazione del MICRO SWITCH finecorsa globali (Serie GLS-DIN)
Instruções de Instalação para o MICRO SWITCH de limite global (Série GLS-DIN)
m WARNING
IMPROPER INSTALLATION
•
Consult with local safety agencies and their
requirements when designing a machine-control link,
interface, and all control elements that affect safety.
•
Strictly adhere to all installation instructions.
Failure to comply with these instructions could result in
death or serious injury.
MOUNT, WIRE, AND SEAL THE SWITCH
m WARNING
IMPROPER OPERATION
•
Ensure switch actuator achieves sufficient travel for
positive opening of normally closed (NC) contacts to
occur.
Failure to comply with these instructions could result in
death or serious injury.
Ui 600V ac
Ui 300V dc
UL 50041
EN60947-5-1
EN45545-2 HL 3 (GLA & GLF Series switches only)
EN61373 (GLA Series switches only)
1.
Refer to:
•
Page 5 for adjustments.
•
Pages 9 to 18 for specific travel distances for each
switch code, and specifications.
•
Page 5 proper application of limit switches, and switch
mounting dimensions.
2.
Perform adjustments (if desired):
•
Head orientation, page 5.
•
Actuation direction (Figure 2, page 5).
•
Side rotary switches with 90* positive drive levers
(catalog listings ending in A1A, A1B, A5A, A5B) (Figure
3):
- Ensure flats of switch shaft engage groove in
actuator lever.
- Tighten locking screw (A) until tab (B) no longer
moves.
3.
Mount switch using four M5 or #10 screws. Torque screws
to 4,9 Nm to 5,9 Nm [43 in-lb to 52 in-lb].
4.
Remove screws on cover plate.
5.
Connect stranded wire (0,75 mm
or solid wire (0,75 mm
2
tor terminals (use 90 *C wire when ambient temperature is
over 75 *C). Torque switch terminal screws to 0,8 Nm to 1,0
Nm [7 in-lb to 9 in-lb]. Wire strip length should be 7,3 mm
[0.29 in] max.
6.
Seal conduit opening according to instructions in PK
80112.
7.
Reassemble cover plate, and torque cover screws to 0,5 Nm
[4.4 in-lb].
81501
Issue 6
to 2,5 mm
, 18-14 AWG)
2
2
to 1,5 mm
2
, 18-16 AWG) to connec-