Initial configuration

The first time the unit receives the power supply, it will enter into ASSISTANT mode.
The display will show the message In{ flashing with 0.
Step 1:
Select the most suitable InI option based on the type of installation to be carried
out and press SET. The available options will be shown in the following table:
Type of installation
In{
Cold
regulation
0
Demo mode: it displays the temperature but does not regulate the temperature or activate relays.
1
Solenoid
2 Solenoid + compressor
3 Solenoid + compressor
4
Solenoid
5 Solenoid + compressor
6 Solenoid + compressor
7 Solenoid + compressor
8 Solenoid + compressor
9 Solenoid + compressor
10 Solenoid + compressor
11
Solenoid
12 Solenoid + compressor
13 Solenoid + compressor
If options 2, 5, 7, 9 or 12 are chosen, check the configuration of parameter I11 according to the
pressure switch type used. (See diagram included with the device).
Step 2:
Use keys N and Q to enter the desired Set Point value and press SET. The wizard
has finished. The unit will begin to regulate the temperature.
If this is not the first time you initiate the wizard, after completing the last step the
display will show the message dFp (parameters per defect). You may choose
between two options:
0: Only changing the parameters which affect the wizard. The other
parameters will remain the same.
1: All parameters return to their factory setting except those which have been modified by the wizard.
The wizard will not reactivate. To reactivate it, activate Stand-By mode by pressing the m key for 3 seconds
and wait until the unit completely halts regulation (The m indicator will light up permanently) and press in
this order the following keys (one after the other, not at the same time) N, Q, SET.
If the pump down function is active, a certain amount of time may elapse between starting the stand-by
function and the controller stopping (see p. 12).
* o00= in AKO-16523 /16523-V / 16520, o00=0 in AKO-16523P / 16520P / 16523D / 16523L.
Pump
Evaporator
Defrost
Down
fans
No
Electric
Yes
Electric
No
Electric
No
Air
Yes
Air
No
Air
Yes
Hot gas
No
Hot gas
Yes
Reversed cycle
No
Reversed cycle
No
Static
Yes
Static
No
Static
Parameters
Pd o00 I00 I10 I11 I20 I21 d1 d7 F3
Yes
0
*
2
0
0
Yes
1
1
2
7
1
Yes
0
1
2
0
0
Yes
0
*
1
0
0
Yes
1
1
1
7
1
Yes
0
1
1
0
0
Yes
1
1
2
7
1
Yes
0
1
2
0
0
Yes
1
1
2
7
1
Yes
0
1
2
0
0
No
0
*
1
0
0
No
1
1
1
7
1
No
0
1
1
0
0
13
1652H311 Ed.09
1
CORE
CORE
Diagram
to be
used
0
0 20 0
0
A
0
0 20 0
0
B
0
0 20 0
0
B
0
0 20 1
1
A
0
0 20 1
1
B
0
0 20 1
1
B
9
1
5
2
0
C
9
1
5
2
0
C
0
0
5
3
0
D
0
0
5
3
0
D
0
0 20 1
-
A
0
0 20 1
-
B
0
0 20 1
-
B
2
CORE
CORE

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

16523p16523l1652016520p16523d16523-v

Table des Matières