Maintenance
Follow the manufacturer's instructions for the proper use of water preservative.
Inspect eyewash unit
1 . Visually inspect the eyewash unit weekly for cleanliness and proper solution level (per ANSI Standard Z358 .1-2009) .
2 . Activate the eyewash unit each time the solution is replaced to ensure proper operation . If the unit is not working
properly, remove it from the hazard area and contact Bradley Corporation immediately .
• Check the sprayheads' water spray pattern for an even, continuous flow . The sprayheads are attached to the arm
with screws and can be detached from the tray for cleaning or obstruction removal, if necessary, and reattached
(use a ⁹⁄₆₄" hex-head Allen wrench to remove and reinstall the sprayheads) .
• Check the water supply hose at the basin of the eyewash unit for cracks, leaks or wear .
• Check the entire unit for possible water leakage .
• Check the solution for contamination and replace with fresh solution, if necessary .
Clean eyewash unit
When using potable water and water preservative (recommended):
1 . Carefully remove the eyewash tank from the pedestal and drain the water solution from the tank (dispose of
the solution properly) . For ease of draining, the pedestal has a drain hole which will accept a ½" I .D . tube at the
underside of the hole (tube supplied by others) (see page 5 for drain hole location) .
2 . Clean the inside of the tank using warm water and a mild soap product; rinse thoroughly .
3 . Refill the eyewash tank following the procedures outlined in Step 2 found on page 4 . Follow instructions of the
preservative manufacturer for the proper use of water preservative .
4 . Reinstall the eyewash tank following the procedure outlined in Step 2 found on page 4 .
When using potable water only:
1 . Empty the tank any time from once per week to once per month, depending on the quality of your water supply . The
manufacturer is not responsible for variations in the water supply .
2 . Clean the inside of the tank using warm water and mild soap . Rinse the tank thoroughly with warm water .
3 . Refill the eyewash tank with tepid potable water .
To operate eyewash unit
1 . Begin operation by pulling the front flap down and all the way out . This action should automatically activate the water spray .
2 . Hold eyelids open with thumbs and forefingers . Rotate eyes back and forth to ensure a complete rinse . Allow water to bathe both
eyes simultaneously for a minimum of 15 minutes .
3 . Seek medical attention immediately after use .
Do not lean on the eyewash tray when in the opened position. Damage to unit may result.