6. OUTLET AIR

NOTE!
The Cinderella GAS system is required to be vented with with 636-certified pipes and in accordance with the
Canadian Gas Code when installed in Canada. Contact your local tradesman for further instructions.
6.1 MATERIAL SPECIFICATIONS FOR VENT PIPES
The toilet must be installed with straight hard pipes with a smooth inner surface, preferably of a 636-rated PP
quality, with minimum temperature tolerances from 90° Celsius (194° Fahrenheit). Do not use any flexible ducts
or pipes when installing the Cinderella GAS toilet.

6.2 CONNECTING THE VENTILATION PIPE TO THE TOILET

The systems venturi is designed for connecting 110 mm PP quality pipes with
an inner diameter of no less than 102 mm (4 inches). The pipe is to enter 35
mm (1
3/8
inches) onto the toilet venturi. Do not use excessive force when
connecting the pipe, as this may damadge the system. The ventilation must
be attached to the appliance by fastening the gear clamp around the gasket
and pipe. Ensure that the pipe is firmly connected to the appliance before
tightening the gear clamp.

6.3 PIPE SIZES

To ensure proper airflow we reccomend you install the system with 110 mm
pipes with a minimum inner diameter of 102 mm (4 inches), it`s an absolute
requirement to use pipes with inner diameter of no less than 95 mm (3
Cinderella GAS incineration toilet to ensure proper air flow and system functionality.

6.4 CHIMNEY CAP

You must install a chimney cap on top of the outlet pipe for your Cinderella GAS appliance. We recommend that
you use the supplied chimney cap when installing your system. If you need to use another chimney cap, make
sure you consult your nearest Cinderella dealer. Too much restriction in the chimney cap could cause the
system to malfunction.
NB!
The Cinderella GAS toilet must have its own outlet air pipe and it is not permitted to install Cinderella GAS ventilation
with the use of the following:
Wind fan or similar as a replacement for the chimney cap
Flexible ducts or pipes.
Pipes with inner diameter less than 95 mm (3
Bends in addition to the T-bend.
Never use a fine mesh net in the ventilation pipe as this might restrict the airflow in the system.

6.5 SPECIFICATIONS FOR INSTALLING THE CINDERELLA GAS VENTILATION SYSTEM

Maximum length horizontal pipe: 600 mm (2 ft). No bends allowed.
Maximum length vertical pipe 4,000 mm (13 ft) No bends allowed.
Required operation pressure inside ventilation pipes when installed: -10 to -5 Pa
Required system airflow per hour 80-90 m
NOTE!
Make sure that the installation complies with building regulations. If you are unsure, contact a
qualified tradesman.
The T-bend must be accessible when installed, so that the drainage pipe can be
rinsed, and the outlet pipe cleaned.
8
3/4
") .
3
3/4
inches) when installing the