5.2.- Indications, selectors and adjustments of the electronic control BM478*.
In the figure 1 of section 3.1.3. it is showed the location of all indicators.
5.2.1.- Indications per phase.
• LD1. Saving order activated. (Yellow).
• LD2. Acoustic alarm on. (Red).
If this LED is ON, call to Service and Technical Support (S.T.S.). The equipment can still be connected, although the
phase with this led ON doesn't operate and stabilize. This LED goes with an acoustic alarm.
• LD3. The equipment is on Bypass. (Red).
If this LED is ON, call to Service and Technical Support (S.T.S.). The equipment can still be connected, although the
phase with this led ON doesn't operate and stabilize. This LED goes with an acoustic alarm.
• LD4. ILUEST status with LD2 inactive. (Green).
- LD4 off. SAVING status.
- LD4 on. START UP or NOMINAL status.
- LD4 blinking. Output voltage RAMP. From START UP to NOMINAL voltage, from NOMINAL to SAVING voltage or from
SAVING To NOMINAL voltage.
Bypass causes with LD2 blinking (equipment in Bypass). (Green).
- LD4 off. Triac opened.
- LD4 on. Triac short-circuited.
• LD5 ÷ 11. It shows the static switch tap which is triggered. (Red).
5.2.2.- Selectors per phase.
• SW1.
EEPROM redording or normal running. Factory preset. Do not touch.
• SW2.
Speed running / adjustment, see table 1.
ON
–
1
2
3
4
5
• SW1 + SW2. Start up voltage selection. By default the ILUEST has the setting of start up voltage set to a lower voltage
than the nominal (210Vac); to set the start voltage to nominal, follow the below steps:
OFF
1-2-3-4-5
– – –
2-3-4-5
Tensión reducida 1 y velocidad normal
1-3-4-5
1-2-4-5
Tensión reducida 1 y velocidad rápida ajuste
1-2-3-5
1-2-3-4
– – –
Tabla 1. Selectors per phase SW2 for control BM478*.
FUNCIÓN
Saving voltage 1 and normal speed
Saving voltage 2 and normal speed
Saving voltage 1 and fast speed
Saving voltage 2 and fast speed
- 23 -