Prescriptions :
ATEX
II 3G Ex nA nC IIC T4 Gc
Harzardous Areas: An enclosure / cabinet rated min. IP54 must be provided in the final installation.
The enclosure / cabinet must be in accordance with the requirement of EN 60079-0:2009 and/or EN60079-15:2010
DIP switches shall not be used in operation or while a hazardous area may be present
The USB-interface cable has to be secured according to the requirements of EN 60079-15:2010, otherwise a permanent connection /
disconnection or operation is not permitted while hazardous area conditions may be present.
Without meeting the requirements of EN 60079-15:2010, the USB-cable is permitted for installation / maintenance only.
ATTENTION
SEPARATION DES CONNECTIONS UNIQUEMENT EN ATMOSPHERES NON-EXPLOSIBLES !
UTILISER LES COMMUTATEURS UNIQUEMENT EN ZONES NON EXPLOSIBLES !
Le connecteur de signaux utilisé en atmosphère explosible doit être pourvu de fixations supplémentaires afin de répondre à EN 60079-15.