Technical Specifications; Floor Load; Water Composition; Working Clearance - AO Smith IT-1500 Notice D'installation, Mode D'emploi, Notice D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1

1.1 Floor load

1.2 Water composition

1.3 Working clearance

1.4 General
specifications
Contents
Empty weight
Max. floor load
Max. operating pres. tank
Max. operating pres. heat exchanger
Max. water temp. tank
Max. water temp. heat exchanger
Anodes
Capacity heat exchanger
Primary flow 80/60ºC
Pressure loss
Heat exchange surface
IT 1500 / 2000 / 2500 / 3000

Technical specifications

Allow for the water heater's weight and the maximum floor load; refer to the table
"General
specifications").
The water heater is intended for heating drinking water. The drinking water must comply with
the regulations governing drinking water for human consumption. The table gives an
overview of the specifications.
Water specifications
Water composition
Hardness
(alkaline earth ions)
Conductivity
Acidity (pH value)
Note
If the water specifications deviate from those stated in the table, then the tank protection
cannot be guaranteed (4"Warranty").
For access to the water heater, it is recommended that the following clearances are
observed:
around the anode connection: 100 cm.
around the water heater: 50 cm.
top of the water heater: 50 cm
> 1,00 mmol/l:
• German hardness > 5,6 ° dH
• French hardness > 10,0 ° fH
• English hardness > 7,0 ° eH
• > 100 mg/l CaCO
> 125 µS/cm
7,0 < pH value < 9,5
Unit
IT 1500
IT 2000
litres
1550
1800
kg
398
426
kg
1948
2226
kPa (bar)
800 (8)
800 (8)
kPa (bar)
600 (6)
600 (6)
ºC
85
85
ºC
90
90
-
3
3
kW
147
147
l/h
6485
6485
mbar
830
830
2
m
5,2
5,2
(1.4
3
IT 2500
IT 3000
2550
2800
576
600
3126
3400
800 (8)
800 (8)
600 (6)
600 (6)
85
85
90
90
3
3
156
156
6871
6871
695
695
6,0
6,0
23

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

It-2000It-2500It-3000

Table des Matières