5. Parts included list
•
This unit includes the following parts. Please check.
•
For usage methods, refer to item 10.2.
1 Connecting pipe
ID ø25.4 mm, ID ø22.2 mm
[ID ø1 in, ID ø7/8 in]
<Low-pressure side>
Model
P72
P96
P120
6. Space required for unit installation and operation
1 In case of single installation
•
Secure enough space around the unit as shown in the figure below.
[Fig. 6.0.1]
(1) If the distance is 00 mm [11-1/16 in] or more between the rear side
and the wall
<A> Top view
300*
[11-13/16]
450*
A
[17-23/32]
15*
15*
[19/32]
[19/32]
() If the distance is 100 mm [-15/16 in] or more between the rear side and
the wall
<A> Top view
100*
[3-15/16]
450*
A
[17-23/32]
50*
50*
[1-31/32]
[1-31/32]
() If the wall height (H) of the front, rear or side exceeds the wall height
restriction
<B> Side view
B
A
•
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defined here, add the height that exceeds the height
limit <h> to the figures that are marked with an asterisk (*).
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm [19-11/16 in] from the unit bottom
Side: Up to the unit height
2 Connecting pipe
ID ø25.4 mm, OD ø19.05mm
[ID ø1 in, OD ø3/4 in]
<High-pressure side>
-
-
1 pc.
1 pc.
-
1 pc.
(Unit: mm [in])
(Unit: mm [in])
(Unit: mm [in])
3 Connecting pipe
ID ø25.4 mm, ID ø28.58mm
ID ø19.05mm, OD ø19.05 mm
[ID ø1 in, ID ø1-1/8 in]
<Low-pressure side>
-
-
1 pc.
(4) If there are obstacles at the upper part of the unit
<C> When there is little space up to an obstruction
45°
240
[9-15/32]
50
[1-31/32]
Front
Unit height
A
B
Back
Air outlet guide (field-supplied)
C
D
4 Connecting elbow
[ID ø3/4 in, OD ø3/4 in]
<High-pressure side>
-
1 pc.
1 pc.
(Unit: mm [in])
1000
[39-3/8]
D
A
C
5