3. Product information

Fig. A: EHD unit
1
Upper part of housing
2
Terminal box cover
3
Protective grille
4
Terminal box
5
Cable lead-through
6
Connecting terminal
7
Cable grommet
8
Impeller
9
Roof socket
T
Rating plate

3.1 Product description

EHD roof fans are used to extract air from
production facilities and workplaces. For
example from canteens, commercial
premises, labs or even air extraction systems
for machines or workplaces.
EHD units are developed for use in outdoor
areas. They are either fitted on a suitable
base frame with a roof socket or directly on
the air extraction pipe without a roof socket.
EHD units have horizontal air outlet.
They are switched on and off using a
separate switch (this should be supplied by
the customer). The fan unit switches on/off
immediately when the switch is operated.
The speed of EHD units can be controlled,
for example using speed controllers ST..
and STU.., see Maico accessories.

4. Technical data

Permissible maximum
temperature of air medium,
depending on unit model
Rated voltage
and frequency
Degree of protection:
+40 ... +70 °C
230 V, 50 Hz
IP X5 (protected
from jet water
from all directions)
Sufficient supply air intake must be
ensured during operation with air-
ventilated fireplaces.
The maximum permitted pressure
difference per living unit is 4 Pa.

4.1 Dimensions and weights

A
D1
EHD 10
300
EHD 12
300
122
EHD 15
400
147
EHD 16
400
157
EHD 20
400
198
EHD 25
400
248
EHD 31
400
314
Tab. 1: Dimensions (in mm),
Weights "G" (in kg)
4.2 Maximum values for volumetric
flows and static pressure
Air flow
volume
EHD 10
310 m³/h
EHD 12
360 m³/h
EHD 15
560 m³/h
EHD 16
710 m³/h
EHD 20
865 m³/h
EHD 25
930 m³/h
EHD 31
1450 m³/h
Tab. 2: Volumetric flow, Static pressure
For technical data, also refer to the rating
plate.
D2
H
98
333
225
333
225
405
266
405
266
405
266
405
266
484
322
Static
pressure
386 Pa
337 Pa
427 Pa
462 Pa
631 Pa
650 Pa
807 Pa
GB
G
3.1
3.1
4.4
4.4
5.0
5.5
6.0
9