NVM175 Handbook
Primary mains circuits to secondary: 5.66kVDC*
Secondary circuits to earth: 2.515 to 2.525kVDC
*Important Note: This test is not possible with Y capacitors fitted to the unit as damage to these
capacitors may occur.
Routine Dielectric Strength testing is carried out as follows: Primary mains circuit to Secondary circuits and
earth – 2.515kVdc to 2.615kVdc. Secondary circuits to earth 2.25kVdc to 2.35kVdc
Safety Approvals:
UL60950-1, UL62368-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
IEC / EN60950-1 - CE mark.
IEC/EN60950-1, IEC/EN 62368-1 and IEC/EN60601-1 - CB Report and Certificate.
CE marking when applied to any NVM175 or NVM175D product indicates compliance with the Low Voltage
Directive in that it complies with EN60950-1and with the ROHS Directive.
UL/CSA 60601-1 - UL + C -UL approval
Fusing: Internal fuses (F1): dual fuses in the L and N line (except single fuse in the L line for the –FL option),
T3.15AH, 250V, 5x20mm.
Symbols
AC
EARTH
Note: All output voltages/variants may not be available as standard units, refer to datasheet for
standard product range. These (and other variants) may be available as non-standard or custom
units, please contact our sales team for details.
Unit Nomenclature
NVM175 or NVM-175 models as described below:
Units may be marked with a Product Code: X5x or NVM1x where x may be any number of characters.
Unit Configuration Code (Description): may be prefixed by NS # followed by / or - (where # may be any
number of characters indicating non- safety related model differences).
Unit Configuration Code:
NVMxy-abcdefghijklm
Where:
x
= 1 for 175 or 1D (1D for Double insulated or Class II unit)
y
= Blank for Y2 capacitors from output to earth (except 1D models)
P for Y1 capacitors from output to earth (except 1D models)
a
= Number of Outputs: 1.
b
= Channel 1 Output Voltage where: T is for 12V, F is for 15V and G is for 24V.
c
= O (for omit).
d
= O (for omit).
e
= O (for omit).
f
= Standby supply:
Blank for no standby and no remote on/off (enable) or '-' followed by
S for 12V version with power good, logic level high enables main output.
S1 for 12V version with power good, logic level low enables main output.
S2 for 12V version with Channel 1 good, logic level high enables main output.
S3 for 12V version with Channel 1 good, logic level low enables main output.
S4 for 12V 0.8A version with power good, logic level low enables main output.
S5 for 5V 0.5A version with power good, logic level low enables main output.
S6 for 5V 0.5A version with power good, logic level high enables main output.
N
L
N – Neutral
L – Live
Page 14 of 23
+ Positive DC
- Negative DC
17814 issue 17, September 2019