A
Air damper setting (A).
To act on the screw in figure:
• to increase output,
turn screwdriver clockwise
• to reduce output,
turn screwdriver counterclockwise
!
Risk of air blast!
Continuously check CO, CO 2 and soot emissions when adjusting the output of
the burner. Optimise combustion values in the event of CO formation. CO must
not exceed 50 ppm.
Pre-setting diagrams in appendix
Before start-up adjust the burner
parameters according to the settings given
in the diagrams for GAS/LPG.
These values have been determined in
our test labs and are useful for the first
switch-on as final setting must be done
using a combustion analyzer.
How to read and adjust the values:
- determine the output required
- determine the combustion chamber back-
pressure
- read the position of the head in the
diagram and adjust it according.
- read the position of the air flap and adjust
it according.
4,0
7,0
3,5
6,8
6,5
3,0
6,3
2,5
6
5,5
2,0
5,2
5
1,5
4,5
1,0
0 5
0,5
0,0
0
-0,5
1
-1,0
-1,5
3
0
4
0
12
www.ecoflam-burners.com
A
MAX GAS 40 P
Firing head setting (B).
To act on the screw in fi gure:
• turn Allen key till you reach the
requested value (index 0-4,5).
Optimising combustion values
The factory setting shall be modified
according to the output requeired.
The diagrams of air/head setting
that are available in the appendix
of this manual are a guide for ensuring
that the burner functions as well as
possible.
MAX GAS 70 P NATURAL GAS
7,3
7,5
1,5
0
1
5
2
3
5
0
output (kW)
MAX GAS 70-120 P
2
2,5
3
7
9
12
6
0
7
0
B
MAX GAS 40 P
B
MAX GAS 70-120 P
Adjustment of gas solenoid valve
Refer to the gas train manual for the gas
setting of the gas train selected.
Note: observe the minimum required
flue gas temperature specified by the
boiler manufacturer and the
requirements demanded of flue gas
ducts for avoiding condensation.
head gas pressure (on elbow) (mbar)
head position
8
0
air damper position