5.2.2 Explosive gas atmospheres
The intrinsically safe circuits of the DMS inter-
face, type DI05, may be fed into Zone 1explosive
gas atmospheres.
5.2.3 Explosive dust atmospheres
The intrinsically safe circuits of the DMS inter-
face, type DI05, may be fed into Zone 21explo-
sive dust atmospheres. However, it is necessary
to ensure that the apparatus is connected these
intrinsically safe circuits, meets the requirements
of EPL Db (Zone 21) and is marked accordingly.
5.2.4 Installation in areas requiring EPL Gc
5.2.4.1Enclosure
The plug-in terminals for the non-intrinsically
safe circuits and the potential equalization con-
ductor must not be disconnected when live.
5.3
Interconnection
The interconnection with intrinsically safe appa-
ratus shall be tested according to the technical
rules and regulations (see also CEC Part I and
NEC).
6.

Inspection and maintenance

The valid operating manual of the manufac-
turer shall be ob served for inspection, main-
tenance and repair. During servicing, it is par-
ticularly important to check those compo-
nents upon which the type of protection
depends.
The functional characteristics of the apparatus
shall remain stable over long periods of time,
thus eliminating the need for regular adjustment
or similar. Also, no other maintenance work is
required.
As soon as malfunctions are observed, disas-
semble the apparatus. Internal parts cannot be
serviced by the customer. Return the apparatus