Installing Several Detectors In A Network - hager TG 500A Guide D'installation

Masquer les pouces Voir aussi pour TG 500A:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1

Installing several detectors in a network

It is possible to inter-connect up to 40 detectors to make alarm activation possible over the
whole range of smoke detectors of the home.
1. After the detector's mounting base has been nstalled, unfasten the connector block.
2. Then do the wiring as follows:
TG 500A / TG 500B
For a cable of 1.5 mm csa, the distance shall not exceed 400 m.
3. Fasten the connector block back onto the supporting base.
4. Lock the detector on its base.
Connect only detectors of the same model within the network.
To install TG501 detectors in a network, an asymmetric power supply can be used.
A separate cutout should be used for protection in this case.
30
TG 501A

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Tg 500alTg 500bTg 501aTg 501al

Table des Matières