Télécharger Imprimer la page

S+S Regeltechnik HYGRASGARD DFF Notice D'instruction page 7

Masquer les pouces Voir aussi pour HYGRASGARD DFF:

Publicité

Les langues disponibles

Les langues disponibles

G
®
HYGRASGARD
Connecting diagram
Output:
0 -10 V
230V AC
24V AC/DC
1 2 3 4
NOTE
At transmitters with current output the humidity output (Pin 2)
must categorically be connected !
®
HYGRASGARD
DFF
HYGRASGARD
®
DFTF
Type ⁄ WG01
Measuring Range ⁄ Readout
Humidity
DFF - I
D F F - I
0...100 % r. H.
D F F - I LCD
0...100 % r. H.
DFF - U
D F F - U
0...100 % r. H.
D F F - U LCD
0...100 % r. H.
DFTF - I
DFTF-I
0...100 % r. H.
DFTF-I LCD
0...100 % r. H.
DFTF - U
DFTF-U
0...100 % r. H.
DFTF-U LCD
0...100 % r. H.
Optional:
Cable connection with M12 connector according to DIN EN 61076-2-101
DFF ⁄ DFTF
DFTF - xx - U
Connecting diagram
with ⁄ without
Output:
display
4...20 mA
230V AC
PLC
PC
24V DC
In-ceiling humidity sensors (± 2.0 %), Premium
In-ceiling humidity and temperature sensors (± 2. 0 %), Premium
Temperature
–35...+75 °C
–35...+35 °C
0...+50 °C
0...+80 °C
(4 x as above)
(4 x as above)
(4 x as above)
DFTF - xx - I
with ⁄ without
display
PLC
Working
resistance
1 2 3 4
Output
Humidity
Temperature
4...20 mA
4...20 mA
0 -10 V
0 -10 V
4...20 mA
4...20 mA
4...20 mA
4...20 mA
0 -10 V
0 -10 V
0 -10 V
0 -10 V
Load resistance diagram
800
Load resistance diagram
4...20 mA
Load resistance diagram
700
600
800
500
700
400
600
300
500
250
200
400
50
10
300
250
Operating voltage (V DC)
200
50
10
15
20
25
Operating voltage (V DC)
NOTE
For 4...20 mA devices, DC voltage must be used
(without residual ripple, see permissible range of load
resistance diagram). Do not use pulsating DC voltage.
Temperature
measuring ranges
(adjustable)
– 35...+ 75 °C
– 35...+ 35 °C
0...+ 50 °C (default)
0...+ 80 °C
Display
Item No.
I - variant
12 01-6132- 0000- 100
1201- 6132- 0200-100
U - variant
12 01-6131- 0000- 100
1201- 6131- 0200-100
I - variant
1201- 6132- 1000- 100
1201- 6132- 1200-100
U - variant
1201- 6131- 1000-100
1201- 6131- 1200-100
Rev. 2021 - V13
DFF
DFTF
Admissible
range
Admissible
range
15
20
25
30
35 36 4
30
35 36 40
DIP
DIP
1
2
O N
O N
OFF
OFF
OFF
O N
O N
OFF
on request

Publicité

loading

Ce manuel est également adapté pour:

Hygrasgard dftfHygrasgard dff-i