Troubleshooting - Honeywell TrueCLEAN FH8000A1620 Guide D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Troubleshooting

WARNING: Electrocution Hazard.
Failure to follow this warning could result in personal injury or death.
The following procedures will expose electrical components. Before servicing, always turn off main power
to system. There may be more than one disconnect switch.
CAUTION: Personal Injury Hazard.
Failure to follow this caution may result in personal injury.
The following instructions are for use by qualified personnel only.
The Honeywell Enhanced Air Cleaner is equipped with a power indicator light located on the door (see Fig.
17 on page 19). This power indicator light illuminates when the Honeywell Enhanced Air Cleaner door is
installed, the power switch is in the on position, AND the air handler blower or furnace blower is running
and (for 1620, 2020, and 2520) airflow is sensed. If the power indicator light is not illuminated, follow the
troubleshooting steps below.
1.
Check that the Honeywell Enhanced Air Cleaner door is installed.
NOTE:
A magnet in the door (see Fig. 16 on page 19) is used to activate a safety switch in the power
supply when the door is installed. The power supply will not energize the air cleaner unless the
safety switch is activated.
2.
Check that the Honeywell Enhanced Air Cleaner power switch is in the ON position.
3.
Confirm that the heating and cooling system blower is operating.
4.
Confirm that power is provided.
Models 1620/2020/2520: 208 to 230 VAC.
Models 1625/2025: 120 VAC.
5.
Models 1620/2020/2520 ONlY:
(see Fig. 11 on page 15).
NOTE:
Even though power is supplied to the Honeywell Enhanced Air Cleaner, it will not turn on unless
the airflow sensor senses airflow or the airflow sensor's bypass plug is inserted.
a.
If still not functioning, disconnect the airflow sensor cable and the power cord from the power
supply.
b.
Remove the enhancement module from the Honeywell Enhanced Air Cleaner cabinet and inspect
the airflow switch (see Fig. 14 on page 16).
c.
Confirm the airflow switch is properly seated in its bracket and the airflow switch cable is
connected to the back of the switch. Replace the enhancement module.
d.
Reconnect the power cord to the power supply and temporarily insert the airflow sensor disable
jumper (from parts bag).
e.
If the power indicator light illuminates, then replace the airflow sensor.
22
Confirm that the airflow sensor cable is connected to the power supply
TrueCLEAN™ Enhanced Air Cleaner
68-0308EFS—01