5.0 Controls
Note: When increasing the heating set-point beyond the cooling set
point, the cooling set point will increase in line with the heating
set-point. Additionally, if the heating set-point is increased further
until it reaches the cooling set-back temperature, the set-back
temperature will also increase with the heating set-point.
Display
1.
Heating indicator
2.
Cooling indicator
3.
Temperature symbol – when this is displayed
the current room temperature is displayed
4.
Fan speed symbol (fan blades will rotate when active)
5.
Comfort setting
6.
Power (on/off)
7.
Clock setting
8.
Room temperature
9.
Time
10.
Day of the week
11.
Auto setting (to follow set programme) - Full mode only
12.
Night set-back setting - Full mode only
13.
Holiday setting - Full mode only
14.
Program menu - Full mode only
15.
Program schedule - Full mode only
Keys:
OK
Validation key (OK)
+
Plus key (up)
-
Minus key (down)
Navigation left
Navigation right
Unit Operation
Turn on Electrical Supply
Press & hold (+) & (-)
for 5 secs to change
Easy Mode
between modes
(Factory Default)
Select Clock
Set Time
Select Comfort Setting
Set room temperature to
desired setting (default 21°C).
Fan runs in heating/cooling
04
Similarly, when decreasing the cooling set point below the heating
set-point, the heating set point will decrease in line with the cooling
set-point, and if the cooling set-point is decreased further until it
reaches the heating set-back temperature, the heating set-back
temperature will also decrease with the cooling set-point.
Full Mode
Use ( ) and ( ) keys to select
operating mode (Refer to
table on page 5)
Select Auto mode and
press (OK) for 10 secs
Setup Parameters
(Refer to table on page 6)
EN
EN
5.0 Controls
(continued...)
Operating Modes
Use (
) and (
) keys to choose from the following parameters. A function is selected when the icon is surrounded by
Function
Description
Control Operation Setup
The unit must be programmed for operation
in heating only, cooling only or heating and
cooling.
Fixed Fan Setting
F1, F2, F3 gives fan speed 1,2 or 3 respectively
with no temperature control.
Comfort Setting
Provides room temperature control with
automatic fan speed adjustment according to
difference between actual and set temperature.
The fan operates when water ≥32°C in heating
or ≤15°C cooling or selected set points.
Automatic Setting
The unit will run according to one of the 9
Auto
preset timed programs, or one of the 4 user
defined programs.
Night Set-back Setting
Provides room temperature control with
automatic fan speed adjustment according
to difference between actual and night set-back
temperature.
Holiday Function
Provides frost protection or overheat protection
during periods of absence (holiday). The control
will count down the time to "00" after which
control is resumed in Auto setting. For frost
protection the set temperature is 7°C.
For overheat the set temperature is 30°C.
Power On/Off
Turns unit on/off.
Set Clock Menu
Displays time in 12h or 24h format.
Program Menu
Provides choice from 9 pre-programed and
P
4 user defined timed programs.
Availability
Adjustment
Easy
Control Operation Setup
Scroll to the Fixed Fan mode
, and then
press on the (
) key.
Use (+) or (-) keys to choose from
No
the following:
Nod (Mode) HOt for heating.
Nod (Mode) COLd for cooling.
Nod (Mode) AUtO for heating and cooling.
Press (OK) to confirm.
Use (+) or (-) to select and press (OK) to confirm.
(Note the fan speed symbol will only appear
when the fan is running).
Yes
Press (OK) to view the set temperature.
Use (+) or (-) to adjust the required room
temperature. Default setting is 21°C in Heating
Yes
and 22°C in cooling.
See page 6 for program options
and setup.
No
Press (OK) to view the actual set
temperature (Comfort or Set-back).
Press (OK) to view the set temperature.
Use (+) or (-) to adjust the required room
temperature. Default setting is 19°C in
No
Heating and 24°C in cooling.
Select
and is
displayed.
Use the (+) and (-) to adjust the duration.
(In hours "H" if below 24H and then in
days "d").
No
Use the (-) key to interrupt this period
and adjust the duration on "no".
Press (OK) to turn the power on or off.
Yes
Press (OK)
Use the (+) and (-) keys to set the minutes.
Press (OK)
Yes
Use the (+) and (-) keys to set the hours.
Press (OK)
Use the (+) and (-) to set the days. Press (OK).
See page 6, program mode.
No
05
.
Full
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes