Télécharger Imprimer la page

Afriso EURO-INDEX 11500 Notice De Montage page 5

Masquer les pouces Voir aussi pour 11500:

Publicité

Les langues disponibles

Les langues disponibles

Technical Data
1. CONTINUOUS READOUT
2. INDICATION:
3. TANKS:
4. FUEL:
5. MOUNTING:
Commissioning
1. Float adjustment
2. Instrument adjustment
Unimes
The UNIMES universal mechanical level gauge with continuous
readout can be installed on any tank of any shape with a height
or diameter between 90 and 200 cm.
Only a G1½ or G2 connection nozzle ist required.
in percentage of total height (or in litres, with a special scale
which is available to order)
installed in cellar, any shape, height 90 to 200 cm
fuel oil
double thread, G2 - G1½
Commissioning consists of three stages:
- float adjustment
- instrument adjustment
- installation on tank
The float line ist fitted with three weights. Two of the weights are
fixed, one (1) at the end of the line and one (2) 15 cm above the
end. An adjustable weight (3), which ist used to fix the float in
position, ist fitted between the two fixed weights.
For tanks without manoles or flanged nozzles:
Push the float up to weight 2 and press weight 3 tight. The float
is then fixed in position.
During production, the UNIMES universal mechanical level
gauge is set to its maximum useful measuring range, correspon-
ding to a tank with a height or diameter of 200 cm.
For tanks with manholes or flanged nozzles:
The distance by which the manhole or flan-
ged nozzle projects above the tank must be
taken into consideration with reference to the
length of the line.
Measure this distance from weight 2 in the
direction of weight 1 and mark it on the line.
Push the float up to this mark and fix it in
position using weight 3.
5

Publicité

loading