3.3.4 Output neutral system
The equipment output is delivered from its floating mechanical ground (IT system). Only casing ground is connected to
the output terminal PE.
* If keeping IT neutral system, install an insulation monitoring device between the output phase and installation
ground.
* If the desired neutral system is TT (earthed neutral) :
- Connect the output neutral to the output PE cable by installing the green/ yellow jumper between the X18 and
X24 Faston terminals.
- Install a bipolar 30mA fault current protection switch between phase an neutral (caliber 16A for 230VAC or
32A for 115VAC).
3.3.5 Boat wintering
When the boat is out of water (dockside maintenance, wintering, extended storage), output protection PE cable
must be connected to the input one.
For this operation, move the green/ yellow cable near the input terminals from X17 Faston terminal to X11 Faston
terminal.
CAUTION:
when back to the sea, restore the original configuration to ensure galvanic isolation.
4 TECHNICAL SPECIFICATIONS
Features
Input voltage
Commutation
Output voltage
Frequency
Current
Soft-start
Ambient temperature
Ventilation
Humidity
Transformer type
Casing material
Degree of protection
Standards
Weight (Kg)
Dimensions : h x L x l
mm
IT3600M
(Manual)
115/230VAC
Manual
115/230VAC
50/60Hz
16/32A
Yes
From -20°C to +40°C
Half speed (reducing acoustic noise)
95% without condensation
Toroidal
Steel with anti-corrosion treatment
IP21
IEC 60076
24
400 x 300 x 200
IT3600A