3 INSTALLATION
This paragraph deals with installation-related arrangements. See section §.1.1.
C
3.1
ASING FIXING
3.2
WIRING
3.2.1 Choosing input and output cables
Input and output cables must have Phase, Neutral and yellow / green protection (PE) conductors.
These conductors must meet the minimum sections indicated in the table below. The values can be increased up to 6
mm² to reduce, in-line voltage drop (maximum section acceptable by the equipment terminals).
Equipment power
3600W
Single phase supply voltage
115/120 VAC
230/240 VAC
Casing external dimensions :
400 x 300 x 200 mm
Fixings :
4 x M8 screws
Conductors minimum
section
6 mm²
2.5 mm²
Current consumption at
rated power
32A
16A
21