Isolation Transformer Coupling; Manual Coupling » Devices - Cristec IT3600 Manuel Utilisateur

Publicité

Les langues disponibles

Les langues disponibles

I
3.3
SOLATION TRANSFORMER COUPLING
As indicated in the previous table, and depending on their configuration, these devices are designed to accept two
types of power supply networks, 115VAC or 230VAC. Similarly, they can provide a 115VAC or 230VAC voltage on the
distribution output.
Therefore, it is necessary to choose couplings carefully before powering on.
3.3.1 « MANUAL COUPLING » devices
First, input and output manual version (IT3600M) must be configured using cables provided in the accessory bag.
These cables must be installed on faston plugs on the electronic control board.
To achieve the couplings, comply with the instructions below (see the label on the protection plate).
Install the provided jumper accessory to select the Led indicator corresponding to the selected coupling.
* Input coupling must be done in accordance with the power supply voltage available, at the risk of equipment
damage.
* Output coupling must be done in accordance with on board need. An error, in the choice could cause the
destruction of the on-board piece of equipment.
Input
coupling
115VAC input and/or output voltage configuration :
Select the 115VAC corresponding Led, connect X25 to X1 :
230VAC input and/or output voltage configuration :
Select the 230VAC corresponding Led, connect X25 to X26:
CAUTION
Output
coupling
Input network
indicator Led
23