Télécharger Imprimer la page

S+S Regeltechnik THERMASGARD MWTM Notice D'instruction page 6

Masquer les pouces Voir aussi pour THERMASGARD MWTM:

Publicité

Les langues disponibles

Les langues disponibles

G
®
THERMASGARD
Calibratable mean-value temperature measuring transducer THERMASGARD
continuous output, in an impact-resistant plastic housing with quick-locking screws, optionally with/without display, with bendable sensor rod (fully active),
protective tube made from copper, plastic-coated, and anti-kink spring, incl. mounting flange. Calibratable mean-value temperature measuring transducer
THERMASGARD
®
MWTM-SD (rod sensor 3 m / 6 m) with eight switchable measuring ranges, continuous output, in an impact-resistant plastic housing
with snap-on lid, with bendable sensor rod (fully active), protective tube made from reinforced thermoplastic hose and anti-kink spring, incl. mounting flange.
The sensor is used to detect the mean temperature (mean value) in gaseous media, e.g. in ventilation and air conditioning ducts over the entire cross
section or over a defined length. Laid along a meandering route, it uniformly detects the surrounding temperature, as a duct temperature sensor. For
proper mounting of the rod, mounting clamps MK-05-M (accessories) are available.The sensor is factory-calibrated; an environmental precision adjustment
by an expert is possible.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance:
R
Load resistance:
R
Power consumption:
< 1.0 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
Sensor:
Pt1000, DIN EN 60751, class B
Measuring ranges:
multi-range switching with 8 switchable measuring ranges, see table (other ranges optional)
T
Output:
0 - 10 V or 4...20 mA
Connection type:
2- or 3-wire connection
Sensors:
active across the entire length (averaging)
Rod material:
protective tube made from copper, plastic-coated (MWTM) (made from reinforced thermoplastic hose for the MWTM-SD),
with anti-kink spring and sleeve, stainless steel V4A (1.4571)
Rod dimensions:
Ø = 5.0 mm, nominal length (NL) = 0.4 m ⁄ 3 m ⁄ 6 m, see table (nominal length optionally up to max. 20 m)
Rod laying:
Bending radius: > 35 mm
Vibration load: ≤ 0.5 g
Tensile load:
Housing:
plastic, UV-resistant, material polyamide, 30 % glass-globe
reinforced, with quick-locking screws (slotted ⁄ Phillips head
combination), colour traffic white (similar to RAL
housing cover for display is transparent!
Housing dimensions:
72 x 64 x 37.8 mm (Tyr 1 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
Cable connection:
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable,
max. inner diameter 10.4 mm) or M12 connector
according to DIN EN 61076-2-101 (optional on request)
Electrical connection:
0.14 - 1.5 mm² via terminal screws on circuit board
Process connection:
by mounting flange, plastic (galvanised steel optional,
see accessories) and mounting clamps MK - 05 - M
Ambient temperature:
measuring transducer –30...+70 °C
Humidity:
< 95 % r. H., non-precipitating air
Protection class:
III (according to EN 60 730)
Protection type:
IP 54 (according to EN 60 529) for the MWTM-SD
IP 65 (according to EN 60 529) for the MWTM
housing tested, TÜV SÜD, report no. 713139052 (Tyr 1)
Standards:
CE conformity, electromagnetic compatibility according to EN
61326, according to EMC directive 2014 ⁄ 30 ⁄ EU
Optional:
Two-line display with illumination, cutout approx. 36 x15 mm
(W x H), for displaying the ACTUAL temperature and the
internal diagnostics (measuring range exceeded, measuring range
not reached, sensor breakage, sensor short circuit)
THERMASGARD
®
MWTM-SD ⁄ MWTM
Type ⁄ WG01B / WG01
MWTM-SD with rod made from reinforced thermoplastic hose, Standard
M W T M - S D - I 3 m
M W T M - S D - I 6 m
M W T M - S D - U 3 m
M W T M - S D - U 6 m
MWTM with rod made from copper, plastic-coated, Premium
M W T M - I 0,4 m
M W T M - I 3 m
M W T M - I 6 m
M W T M - U 0,4 m
M W T M - U 3 m
M W T M - U 6 m
Extra charge:
Optional:
MWTM ⁄ MWTM-SD
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant
a
b
> 5 kOhm for U variant
L
+80 °C with manual zero point correction (± 10 K)
–30 °C, T
min
max
< 480 N for the MWTM
< 100 N for the MWTM-SD
Mean-value temperature measuring transducer
Sensor
Output
Pt1000
4...20 mA
Pt1000
4...20 mA
Pt1000
0 - 10 V
Pt1000
0 - 10 V
Pt1000
4...20 mA
Pt1000
4...20 mA
Pt1000
4...20 mA
Pt1000
0 - 10 V
Pt1000
0 - 10 V
Pt1000
0 - 10 V
Other ranges optional, Two-line display with illumination
Per meter sensor cable (from 6 m to max. 20 m)
Cable connection with M12 connector according to DIN EN 61076-2-101
®
MWTM (rod sensor 0.4...20 m) with eight switchable measuring ranges,
Display and internal diagnostics
9016),,
Rod length
3,0 m
6,0 m
3,0 m
6,0 m
0,4 m
3,0 m
6,0 m
0,4 m
3,0 m
6,0 m
Rev. 2021 - V18
Standard
Measuring range
exceeded
Measuring range
not reached
Sensor
breakage
Sensor
short circuit
Item No.
IP 54
1101- 3132- 0239-90K
1101- 3132- 0269-90K
1101- 3131- 0239-90K
1101- 3131- 0269-90K
IP 65
1101- 3132- 0089-900
1101- 3132- 0239-900
1101- 3132- 0269-900
1101- 3131- 0089-900
1101- 3131- 0239-900
1101- 3131- 0269-900
on request
on request

Publicité