5.6 Alarm Messages

Alarms may be rearmed either automatically or manually.
The following Alarm Messages may appear on the screen:
Serious Error
Power Failure
Serious Error
Thermal
Serious Error
High Pressure
Serious Error
Low Pressure
Serious Error
Probe Failure W
Serious Error
Probe Failure CO
Serious Error
Probe Failure EV
Serious Error
Flow Failure
Serious Error
Repeated Failure
© ASTRALPOOL 2010. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
System power failure.
The order of the three phases is inverted.
Automatically and immediately rearms when the problem is solved.
The thermal circuit is open. Failure in the thermal system.
Semi-automatically rearmed when the problem is solved and the
MODE key is pressed.
The high pressure switch indicates the circuit is open.
Pressure is too high.
Semi-automatically rearmed when the problem is solved and the
MODE key is pressed.
The high pressure switch indicates the circuit is open.
Pressure is too low.
Semi-automatically rearmed when the problem is solved and the
MODE key is pressed.
Failure in the water sensor reading.
Automatically and immediately rearms when the problem is solved.
Failure in the condenser sensor reading.
Automatically and immediately rearms when the problem is solved.
Failure in the evaporator sensor reading.
Automatically and immediately rearms when the problem is solved.
No water flow.
Automatically and immediately rearms when the problem is solved.
If there is a failure in the thermal sensor or the pressure switches,
retry up to three times daily.
Manual rearming with technical assitance.

Figure 15: Alarm messages.