G
®
THERMASGARD
Calibratable room pendulum temperature measuring transducer (with sleeve) THERMASGARD
continuous output, in an impact-resistant plastic housing with quick-locking screws, optionally with ⁄ without display, cable sensor with stainless steel
sleeve and plastic sinter filter (exchangeable). The pendulum sensor has been specially designed to detect the temperature in larger rooms or halls.
The resistance thermometer achieves a very good representative measurement result due to its positioning in the room. The sensor is factory-
calibrated; an environmental precision adjustment by an expert is possible.
Calibratable room pendulum temperature measuring transducer (with globe) THERMASGARD
continuous output in an impact-resistant plastic housing with quick-locking screws, optionally with ⁄ without display, cable sensor with a black plastic
globe. The pendulum sensor has been specially designed to detect the temperature in larger rooms or halls. The resistance thermometer (globe
thermometer) achieves a very good, representative measurement result due to its positioning in the room. The dark radiation sensor determines the
effective radiation heat at the measured location. This is relevant for calculating the thermal comfort (operative room temperature) taking into
account the co-action of thermal radiation and thermal convection. The ratio of globe temperature / air temperature is approx. 70% / 30%. The
sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance:
R
Load resistance:
R
Power consumption:
< 1.0 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
Sensor:
Pt1000, DIN EN 60751, class B
Measuring ranges:
multi-range switching with 8 switchable measuring ranges
see table (other ranges optional)
T
Deviation, temperature:
typically ± 0.2 K at +25 °C
Output:
0 - 10 V or 4...20 mA
Ambient temperature:
measuring transducer –5...+60 °C
Connection type:
2- or 3-wire connection
Protective tube:
RPTM1 stainless steel V2A (1.4301), Ø =16 mm, NL = 142 mm
Sensor protection:
RPTM1 plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Globe:
RPTM2 plastic, colour black, Ø = 50 mm
Housing:
plastic, UV-resistant, material polyamide, 30 % glass-globe
reinforced, with quick-locking screws (slotted ⁄ Phillips head
combination), colour traffic white (similar to RAL
housing cover for display is transparent!
Housing dimensions:
72 x 64 x 37.8 mm (Tyr 1 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
Cable connection:
cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (on request)
Electrical connection:
0.14 -1.5 mm², via terminal screws
Connection cable:
PVC, H03V V-F, 2 x 0.5 mm
K L = approx. 1.5 m (other lengths optional)
Humidity:
< 95 % r. H., non-precipitating air
Protection class:
III (according to EN 60 730)
Protection type:
IP 67 (according to EN 60 529) Housing tested,
IP 65 (according to EN 60 529) Pendulum with globe
Standards:
CE conformity, electromagnetic compatibility according to
EN 61326, according to EMC directive 2014 ⁄ 30 ⁄ EU
Optional:
Two-line display with illumination, cutout approx. 36 x15 mm
(W x H), for displaying the ACTUAL temperature and the
internal diagnostics (measuring range exceeded, measuring
range not reached, sensor breakage, sensor short circuit)
®
THERMASGARD
RPTM
Type ⁄ WG01
Sensor
RPTM 1
R P T M1- I
Pt1000
R P T M1- U
Pt1000
RPTM 2
R P T M 2 - I
Pt1000
R P T M 2 - U
Pt1000
Extra charge:
Other ranges optional Two-line display with illumination
2-wire connecting leads, per running meter (PVC)
Cable connection with M12 connector according to DIN EN 61076-2-101
ACCESSOIRES
SF-M
Metal sinter filter, Ø 16 mm, L = 32 mm, exchangeable,stainless steel V4A (1.4404)
RPTM
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant
a
b
> 5 kOhm for U variant
L
–5 °C, T
+60 °C, with manual zero point correction (± 10 K)
min
max
2
,
TÜV SÜD, Report No. 713139052 (Tyr 1)
Pendulum room temperature measuring transducers
Output
4...20 mA
0 - 10 V
4...20 mA
0 - 10 V
®
RPTM 1 with eight switchable measuring ranges,
®
RPTM 2 with eight switchable measuring ranges,
9016),,
Type
Remote sensor
Remote sensor
Remote sensor
Remote sensor
RPTM 1 = Rev. 2021 - V26
RPTM 2 = Rev. 2021 - V16
Display and internal diagnostics
Standard
Measuring range
exceeded
Measuring range
not reached
Sensor
breakage
Sensor
short circuit
Item No.
with metal sleeve
1101- 1162-0 219-910
1101- 1161- 0219- 910
with globe
1101- 1172-0 219-910
1101- 1171- 0219- 910
on request
on request
7000- 0050-2200 -100