TECHNICAL FEATURES
Thermal power – output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC Directives: Electromagnetic Compatibility 2014/30/UE,
Low Voltage 2014/35/UE, Machines 2006/42/EC.
The burner meets protection level of IP 40, EN 60529.
8
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air damper
7 – Hydraulic jack with air damper
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Combustion head adjustment screw
2347
28 – 60 kW
Gas oil, max. viscosity at 20 °C: 6 mm
Single phase, 230 V ± 10%
Run current 0.75 A – 2850 rpm – 298 rad/s
4 F
Secondary 8 kV – 16 mA
Pressure 7 – 15 bar
0.185 kW
Fig. 1
7
6
6
9
D8067
HYDRAULIC JACK OPERATION 7)(Fig. 1)
DANGER
1
GB
2.3 – 5 kg/h
2
/s (1.5 °E)
~
50Hz
2
It is strongly recommended a periodic check of
the pump pressure operation (annually or bet-
ter every six months, if the burner operation is
continuous).
If the value is lower than 1 bar, compared to
that one of the initial setting, please check the
cleaning of the pump and line filters.
In case the pressure setting was not restora-
ble, please replace the pump, in order to guar-
antee that the pump pressure during the pre-
purge time is at least 3.7 bar.