Safety Instructions; Conformity With Standards; Field Of Application - Eaton CROUSE-HINDS Série Mode D'emploi

Fiches et prises de 32 a, à 4 pôles, 5 pôles, pour atmosphères explosives
Masquer les pouces Voir aussi pour CROUSE-HINDS Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1
Technical data
Supply terminal:
Wall socket GHG 512
Flange socket GHG 512
Coupler GHG 512
Plug
GHG 512
Plug
GHG 532
Test torques:
Cover screws
Terminals
Self-cutting screws size 4
Self-cutting screws size 5
Weight:
Wall socket
4-polig
Plug
4-polig
Coupler
4-polig
Flange socket
4-polig
Wall socket
5-polig
Plug
5-polig
Coupler
5-polig
Flange socket
5-polig
Auxiliary contact, rated voltage:
Auxiliary contact, rated current:
2

Safety instructions

Target group:
For skilled electricians and suitable qualified, instructed
personnel in accordance with national legislation, including
the relevant standards and, where applicable, in acc. with
IEC/EN 60079-14 on electrical apparatus for explosive atmospheres.
The GHG 512 plugs and sockets are not suitable for Zone 0 and Zone
20 hazardous areas. The temperature class and explosion group
marked on the apparatus shall be observed.
Modifications to the plugs and sockets or changes of their design are
not permitted.
They shall be used for their intended purpose and in perfect and
clean condition.
The requirements of the IEC/EN 60079-31 regarding excessive dust
deposits and temperature to be considered from the user.
To ensure adherence to the temperature class stated on the type
label of the apparatus, the permissible ambient temperature, the
rated terminal cross section and the self heating of the apparatus
that is mainly due to the power dissipation shall be taken into
account (test criterion for the self heating is an overload of 10%).
For replacement and repair only genuine COOPER CROUSE-HINDS
spare parts shall be used.
Repairs that affect the explosion protection, may only be carried out
by COOPER CROUSE-HINDS or a qualified electrician in compliance
with the respective national regulations.
Prior to taking the plugs and sockets into operation, they will have to
be checked in accordance with the instruction as per section 6.
The sockets may only be used with the associated COOPER
CROUSE-HINDS plugs in undamaged condition.
The interlocking switch of the socket is mechanically secured and
cannot be connected without plug.
8
Explosion protected plug and socket system
32 A, GHG 512
GHG 512 44
GHG 512 74
GHG 512 34
GHG 512 84
GHG 512 45
GHG 512 75
GHG 512 35
GHG 512 85
Cross section
Stripped wire length
2 x 4.0 - 10 mm²
12 mm
2 x 4.0 - 10 mm²
12 mm
2 x 4.0 - 10 mm²
12 mm
1 x 1.0 - 6,0 mm²
10 mm
1 x 1.0 - 6,0 mm²
10 mm
2.5 Nm
2.5 Nm
2.0 Nm
3.0 Nm
(catalogue version)
approx. 2.25 kg
approx. 0.55 kg / GHG 532 - approx. 1.10 kg
approx. 1.50 kg
approx. 1.00 kg
approx. 2.30 kg
approx. 0.60 kg / GHG 532 - approx. 1.15 kg
approx. 1.60 kg
approx. 1.05 kg
250 V AC
AC / 5 A
DC / 0.03 A
The plugs GHG 532 can further on be inserted with the sockets of
the series GHG 532.
Before the initial operation, any foreign matter will have to be
removed from the the plugs and sockets.
Flange sockets may only be used in protective enclosure or appara-
tus that have been certified for the respective application.
Observe the national safety rules and regulations for prevention of
accidents as well as the safety instructions included in these
operating instructions and set in italics the same as this text!
3

Conformity with standards

The apparatus are conform to the standards specified in the EC-Declara-
tion of conformity, enclosed separately.
References to standards and directives in these operating instructions
always relate to the latest version. Other additions (e.g. details relating to
the year) shall be observed.
4

Field of application

The plugs and sockets GHG 512 are suitable
for use in Zones 1 and 2 as well as in Zones 21 and 22 in accordance with
IEC/EN 60079-10-1 and IEC/EN 60079-10-2.
The enclosure materials employed, including the exterior metal parts, are
made of high-quality materials which ensure a corrosion protection and
resistance to chemical substances corresponding to the requirements in a
"normal industrial atmosphere":
- impact resistant polyamide
- glass-fibre reinforced polyester
- special steel AISI 316 L
In case of use in an extremely aggressive atmosphere, please refer to
manufacturer.
GB