5.3 How to obtain operating data via the VMI LINK PRO application
In order to analyse the product's behaviour, you can download operating data via the VMI® LINK PRO
app > Maintenance tab > VMI® LINK PRO HISTORY button. Enter an email address to receive the
downloaded file. Note you must be sufficiently close to the VMI® to carry out this operation.
5.4 Cleaning and checking
Operation that cannot be done by the user.
5.4.1 Cleaning
The machine must be thoroughly cleaned once a year.
Cleaning the machine:
Cut all power to the VMI® unit before intervening and make sure that it cannot be
accidentally reset.
Open the machine's technical cover by removing the 4 screws.
Cleaning the motor:
o Remove the dust from the fan's wheel using a blower or a dry brush.
o Wipe the inside of the housing with a clean cloth.
o Check the electrical and pneumatic connections.
Cleaning the resistor:
o Remove the dust from the resistor using a blower or a dry brush.
o Wipe the inside of the housing with a clean cloth.
o Check the electrical connections.
Wipe the inside of the housing with a clean cloth.
Check that all the connections are properly connected.
Close the cover again by screwing the 4 screws down again.
5.4.2 Checks
To ensure the appliance remains effective, it is important to check the following points:
-
The condition of the duct system. Clean or change it if necessary.
-
The roof outlet or the suction grille must be clear and not obstructed by anything (nest,
leaves, etc.). If it is obstructed, clean it following the safety rules.
-
The various air passages (openings, grilles, clearance under doors) must not be obstructed or
reduced in size.
39