PREMASGARD
Quality product for HVAC sector, accuracy ± 3 %
®
PREMASGARD
1000 series calibrateable compact pressure sensors are equipped with eight switchable measuring ranges and with
display (4 devices in one) and are used for measuring above-atmospheric, below- atmospheric, or differential pressures in air. The piezo-
resistive measuring element is temperature and pressure compensated and guarantees a high degree of reliability and accuracy. These
pressure transmitters have a pushbutton for manual zero point calibration and an adjustable offset. Applications of these pressure sen-
sors are in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale catering fa-
cilities, for monitoring filters, for level measurement or for triggering frequency converters. Media measured with these pressure trans-
ducers are air (non - precipitating), or other gaseous non-aggressive, non-combustible media. A PREMASGARD
sensor has 4 selectable measuring ranges and therefore, minimizes the diversity of types and stockkeeping while covering a greater
range of applications. The differential pressure sensor is supplied including connection set ASD-06 (2 m connection hose, two pressure
connection nipples, screws).
TECHNICAL DATA:
Power supply: .............................. 24 V AC ⁄ DC for output 0 -10 V ;
Measuring ranges: ..................... multi-range switching with 8 switchable measuring ranges
Output signal: .............................. 0 -10 V or 4... 20 mA
Electrical connection: ................ 2- or 3-wire connection
Media temperature: .................. 0 ... + 50 °C
Pressure connection: ................ 4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm),
Type of pressure: ....................... differential pressure
Medium: ....................................... clean air and other non-aggressive, non-combustible gases
Accuracy: ..................................... ± 3 % of final value (at 20°C)
Zero point offset: ....................... max. + 2.5 % of final value (for voltage output)
Above- ⁄ below-
atmospheric pressure: ............. max. 5 x measuring range
Long-term stability: .................... ± 1 % per year;
Signal filtering: ............................ 1 s
Hysteresis: .................................. 0.3 % of final value
Media contacting parts: ........... brass, Ni, Nylon, PU, Si
Temperature drift values: ......... ± 2.5 % of final value per 10 K
Current consumption: ............... < 20 mA
Linearity: ...................................... ± 2.5 % of final value
Enclosure: .................................... plastic, material polyamide, 30 % glass-globe-reinforced,
Dimensions: ................................. 72 x 64 x 39.4 mm (Thor I )
Electrical connection: ................ 0.14 - 1.5 mm², via terminal screws
Cable gland: ................................. M 16, including strain relief
Humidity: ...................................... < 95 % r. H., non-precipitating air
Protection class: ........................ III (according to EN 60 730)
Protection type:.......................... IP 65 (according to EN 60 529)
Standards: ................................... CE conformity, electromagnetic compatibility
Features: ..................................... illuminated 4-digit display (optional)
ACCESSORIES: ........................... including connection set ASD-06 (nipple straight)
1000
15 - 36 V DC for output 4... 20 mA (depending on working resistance)
see table
metal pressure connection nozzles
rages 25, 50, 100 Pa : 1 Pa
with quick-locking screws, colour pure white (similar RAL 9010)
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC
(included in the scope of delivery)
connection nipple ASD-07 (at 90 degree angle)
pressure outlet DAL-1 for ceiling or
in-wall installation (e.g. in clean rooms)
10
®