Electrical connection
Disconnect the installation from power. Connect the unit as indi-
cated on the terminals. Never connect the minus potentials to
each other or the minus potentials to the FE connection. Ensure
an electrically save ground connection between AS-i controller
(terminal FE) and ground of the unit.
Supply the controller
from the 24 V power supply DN2011 of ifm electronic. The connection
is made to the terminals +24 V and 0 V.
Operating and indicating elements
Information concerning the state of the master (AC1327)/ masters/
AC1337) and the connected system is given via three diagnostic LEDs
on the controller
• LED PWR/COM lights:
• LED PWR/COM flashes: AS-i voltage present, but no slave was
• LED PROJ lights:
• LED PROJ flashes:
• LED CONF/PF lights:
• LED CONF/PF flashes:
Ethernet Status LEDs
• LED Module Status:
green flashes 1Hz:
red flashes 1 Hz:
red flashes 2 Hz:
with a 24 V DC voltage (20...30 V PELV), e.g.
e
.
e
AS-i voltage present, at least one slave
was detected
detected correctly
Projection mode active, the configuration
monitoring is deactivated
Projection mode active, changeover to
protected mode not possible as a slave
with the address 0 is connected
Projected and current configuration do
not match
Periphery fault on at least one connected
slave
The IP address is freely selectable
Invalid MAC ID (internal fault
Ethernet interface)
No valid Ethernet configuration
loaded