Visually check the installation and make sure that:
• Airflow is in the direction of the arrow on the media air filter cartridge.
• Turning vanes and transitions, if used, are properly installed.
• Joints in sheetmetal between media air filter and furnace are sealed.
• All sheetmetal connections are complete.
• Original furnace filter has been removed and blower compartment is cleaned.
When you have verified that checkout has been completed:
• Replace any access doors removed during the Installation or Checkout.
• Run the furnace or cooling system through one complete cycle to make sure the system operates as desired.

Maintenance

The media filter must be replaced when pressure drop across the media filter reaches 0.5 in. w.c. (0.1 kPa), or at
least annually. If the media air cleaner is installed downstream from an atomizing humidifier or if the installation
includes both heating and cooling, more frequent replacement may be necessary. Clogged media must be
replaced promptly to avoid restricting airflow and reducing efficiency of the heating/cooling system. Record the
replacement date in the space provided on the replacement media filter.

Specifications

The specifications in this publication do not include normal manufacturing tolerances; therefore, an individual
unit may not exactly match the listed specifications. This product is tested and calibrated under closely
controlled conditions, and some minor differences in performance can be expected if those conditions are
changed.

FC100A Efficiency

Efficiency Ratings: Based on American Society of Heating, Refrigerating and Air-Conditioning Engineers
Standard 52.2-1999. Efficiency ranges are defined for small particles, E1 = 0.3 to 1.0 micron; medium particles
E2 = 1.0 to 3.0 microns; and large particles, E3 = 3.0 to 10.0 microns.
Efficiency:
E1 = 32% at 492 FPM
E2 = 72% at 492 FPM
E3 = 96% at 492 FPM
Minimum Efficiency Reporting Valve (MERV): 11 at 492 fpm.

Filter Media

Pleated for greater media capacity.
10
F100 Media Air Cleaner 68-0239EF—06