If the malfunction is not caused by one of the above causes, stop the
heat pump immediately. Disconnect the power and contact a local
dealer.
I
MALFUNCTIONING OF THE UNIT AND ERROR CODES
Malfunctioning of the unit and error codes
When an error occurs or the protection mode is set automatically, the circuit board and the wired controller
will both display the error message.
Protection/
Error
LED indicator
Malfunction
code
Standby
Dark
Normal
Bright
running
PP1
Lower
tank
☆●
water temp.
(1flash 1 dark)
sensor failure
PP2
Upper tank
☆☆●
water temp.
(2 flashes 1
sensor failure
dark)
PP3
Evaporator
☆☆☆●
coil
temp.
(3 flashes 1
sensor failure
dark)
Return
air
PP4
☆☆☆☆●
temp sensor
(4 flashes 1
failure
dark)
PP5
Ambient
☆☆☆☆☆●
temp. sensor
(5 flashes 1
failure
dark)
EE1
High
☆☆☆☆☆☆
pressure
●
protection
(6 flashes 1
(HP Switch)
dark)
Possible reasons
1) The sensor open
circuit
1) Check the sensor connection
2) The sensor short
2) Replace the sensor
circuit
1) The sensor open
circuit
1) Check the sensor connection
2) The sensor short
2) Replace the sensor
circuit
1) The sensor open
circuit
1) Check the sensor connection
2) The sensor short
2) Replace the sensor
circuit
1) The sensor open circuit
1) Check the sensor connection
2) The sensor short
2) Replace the sensor
circuit
1) The sensor open
circuit
1) Check the sensor connection
2) The sensor short
2) Replace the sensor
circuit
1) Too high air inlet temp
1) Check if the air inlet temp is
2) Less water in the tank
over the working limited
3)
The
electronic
2) Check if the tank is full of
expansion valve assembly
water. If not, charge water
blocked
3) Replace the electronic
4) Too much refrigerant
expansion valve assembly
5) The switch damaged
4) Discharge some refrigerant
6) The uncompressed gas
5) Replace a new switch
is in refrigerant system
6) Discharge and then recharge
the refrigerant
Corrective actions
22
4