If the malfunction is not caused by one of the above causes, stop the
heat pump immediately. Disconnect the power and contact a local
dealer.
I
MALFUNCTIONING OF THE UNIT AND ERROR CODES
Malfunctioning of the unit and error codes 
When an error occurs or the protection mode is set automatically, the circuit board and the wired controller 
will both display the error message. 
 
Protection/
Error 
LED indicator 
Malfunction 
code 
Standby 
 
Dark 
Normal 
 
Bright 
running 
PP1 
Lower 
tank 
☆● 
water  temp. 
(1flash 1 dark) 
sensor failure   
PP2 
Upper  tank 
☆☆● 
water  temp. 
(2  flashes  1 
sensor failure 
dark) 
PP3 
Evaporator 
☆☆☆● 
coil 
temp. 
(3  flashes  1 
sensor failure 
dark) 
Return 
air 
PP4 
☆☆☆☆● 
temp  sensor 
(4  flashes  1 
failure   
dark) 
PP5 
Ambient 
☆☆☆☆☆● 
temp.  sensor 
(5  flashes  1 
failure 
dark) 
EE1 
High 
☆☆☆☆☆☆
pressure 
● 
protection 
(6  flashes  1 
(HP Switch) 
dark) 
 
 
 
Possible reasons 
 
 
 
 
1) The sensor open 
circuit 
1) Check the sensor connection
2) The sensor short 
2) Replace the sensor 
circuit 
1) The sensor open 
circuit 
1) Check the sensor connection
2) The sensor short 
2) Replace the sensor 
circuit 
1) The sensor open 
circuit 
1) Check the sensor connection
2) The sensor short 
2) Replace the sensor 
circuit 
1) The sensor open circuit
1) Check the sensor connection
2) The sensor short 
2) Replace the sensor 
circuit 
1) The sensor open 
circuit 
1) Check the sensor connection
2) The sensor short 
2) Replace the sensor 
circuit 
1) Too high air inlet temp
1) Check if the air inlet temp is 
2) Less water in the tank 
over the working limited 
3) 
The 
electronic 
2)  Check  if  the  tank  is  full  of 
expansion valve assembly 
water. If not, charge water 
blocked 
3)  Replace  the  electronic 
4) Too much refrigerant 
expansion valve assembly 
5) The switch damaged 
4) Discharge some refrigerant 
6) The uncompressed gas 
5) Replace a new switch 
is in refrigerant system 
6) Discharge and then recharge 
the refrigerant 
Corrective actions